| Plan Review Notes For Permit 11060593 |
| Permit Number |
11060593 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-07-07 08:41:55 | | | | PROVIDE RISER DIAGRAM FOR EXISTING SERVICE EQUIPMENT. | | | NEC 215.5 | | | SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE | | | CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES. | | | FBC 13-415 ABC.1.2. SPACE CONTROL; 13412.ABC.1.3 | | | ADDITIONAL CONTROLS | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|