| Plan Review Notes For Permit 11060515 |
| Permit Number |
11060515 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-06-23 18:29:36 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PLEASE PROVIDE INFORMATION ON HOW YOU HAVE | | | DETERMINED THAT THE BOTTOM SUBSTRATE IS CONCRETE RATHER | | | THAN CONCRETE BLOCK. CBS HOMES TYPICALLY HAVE CONCRETE | | | TOP SUBSTRATE, BLOCK BOTTOM. EITHER PROVIDE REQUESTED | | | INFORMATION OR REVISE BOTTOM SUBSTRATE AND ANCHOR | | | SPACING. | | | | | | 2. PLEASE REVISE SPAN; THIS SHOULD EQUAL BLADE LENGTH | | | (NOT OPENING SIZE). WITH A 2 1/2" EDGE DISTANCE, SPANS | | | SHOULD BE A MINIMUM OF 2" LARGER THAN OPENING SIZES. | | | | | | 3. PLEASE CLARIFY INSTALLATION, "H" IS SPECIFIED; | | | ACCORDION SHUTTERS ARE TYPICALLY INSTALLED VERTICALLY. | | | IF THE CLEAR PANEL IS TO BE INSTALLED HORIZONTALLY, | | | SUBSTRATE IS CONCRETE BLOCK FOR BOTH SIDES (FILLED | | | CELLS ARE BLOCK). | | | | | | 4. THE INSTALLATION SCHEDULE DOES NOT INCLUDE THE SPANS | | | ON THE FIRST SHEET, PLEASE REVISE. | | | |
|