| Plan Review Notes For Permit 11060463 |
| Permit Number |
11060463 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-07-07 09:35:53 | PHASE, AMPACITY, VOLTAGE AND WIRE SIZE NOT CLEARLY | | | INDICATED ON PLANS. SHEET E2 CONFLICTS WITH E5. | | | POWER CONDUCTORS NOT SHOW. CONDUITS MAY BE UNDERSIZED. | | | PROVIDE SPECIFICATION ON THE TRANSFERE SWITCH. PROVIDE | | | A SUMMARY LOAD CALCULATION. NEC 215. 5 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | | | | | | | | | | | | | |
|