| Plan Review Notes For Permit 11060458 |
| Permit Number |
11060458 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-07-05 12:58:38 | 901 45TH STREET | | | PERMIT #11060458 | | | MASTER #11010154 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****PROVISO***** | | | | | | INDICATE ON SHEET FP4.0 THE METHOD BEING USED TO | | | ACCOMPLISH SHUNT TRIPPING THE POWER TO THE ELEVATOR | | | UPON ACTIVATION OF A SPRINKLER LOCATED IN THE ELEVATOR | | | MACHINE ROOM. POWER SHUNT TRIP SHALL BE ACCOMPLISHED | | | WITH HEAT DETECTORS LOCATED WITHIN 2 FEET OF SPRINKLERS | | | OR A FLOW SWITCH DEVICE WITHOUT TIME DELAY | | | CAPABILITIES. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|