Plan Review Notes
Plan Review Notes For Permit 11060444
Permit Number 11060444
Review Stop M
Sequence Number 1
Notes
Date Text
2011-07-19 07:30:47PLAN DENIED
 AHU- A1
 REFER TO SECTION 606.2.1 SUPPLY SYSTEM AND SECTION
 606.3 INSTALLATION.
 2007 FBC (M)
 REFER TO SECTION 13-409.AB.3.3 SHUTOFF DAMPER
 CONTROLS.2007 FBC.
 AHU- 1B
 REFER TO SECTION 607.7 FLEX DUCT PASSING THROUGH A 1
 HR. RATED PARTITION.
 ROOM 117 TO ROOM 116.
 REFER TO SECTION 606.2.1 SUPPLY SYSTEM AND 606.3
 INSTALLATION
 2007 FBC (M)
 AHU- 2
 REFER TO SECTION 601.4 BALANCED RETURN AIR. FOR OFFICE
 104.
 2007 FBC(M)
 AHU-4
 REFER TO SECTION 601.4 BALANCED RETURN AIR. ROOM 101
 RECEPTION.
 2007 FBC (M)
 SEE BUILDING REVIEW NOTES ON CHANGE OF OCCUPANCY, RATED
 CORRIDORS
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]