| Plan Review Notes For Permit 11060444 |
| Permit Number |
11060444 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-07-19 07:30:47 | PLAN DENIED | | | AHU- A1 | | | REFER TO SECTION 606.2.1 SUPPLY SYSTEM AND SECTION | | | 606.3 INSTALLATION. | | | 2007 FBC (M) | | | REFER TO SECTION 13-409.AB.3.3 SHUTOFF DAMPER | | | CONTROLS.2007 FBC. | | | AHU- 1B | | | REFER TO SECTION 607.7 FLEX DUCT PASSING THROUGH A 1 | | | HR. RATED PARTITION. | | | ROOM 117 TO ROOM 116. | | | REFER TO SECTION 606.2.1 SUPPLY SYSTEM AND 606.3 | | | INSTALLATION | | | 2007 FBC (M) | | | AHU- 2 | | | REFER TO SECTION 601.4 BALANCED RETURN AIR. FOR OFFICE | | | 104. | | | 2007 FBC(M) | | | AHU-4 | | | REFER TO SECTION 601.4 BALANCED RETURN AIR. ROOM 101 | | | RECEPTION. | | | 2007 FBC (M) | | | SEE BUILDING REVIEW NOTES ON CHANGE OF OCCUPANCY, RATED | | | CORRIDORS | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|