2011-06-29 11:55:151507 BELVEDERE ROAD
 PERMIT #11060444
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 STRUCTURES WITH LIGHT FRAME ROOF TRUSS CONSTRUCTION
 SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO THE
 BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE LETTER R DESIGNATION PER
 FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE CODE
 69A-60.0081.
  
 PORTABLE FIRE EXTINGUISHERS SHOWN IN CABINETS SHALL
 HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE TAGGED BY
 A LICENSED FIRE EXTINGUISHER COMPANY.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND
 SHALL CONTRAST THE BACKGROUND.
  
 THE OCCUPANCY IS LISTED AS BUSINESS; HOWEVER, THE
 BUILDING IS FUNCTIONING AS A MULTI-USE (BUSINESS AND
 ASSEMBLY) OCCUPANCY. THE BUILDING DESIGN SHALL CONFORM
 TO THE REQUIREMENTS FOR MIXED USE (NON-SEPARATED) OR
 SEPARATED USE AS INDICATED IN SECTION 6.1.14.2 OF NFPA
 101 FLORIDA EDITION 2006. FOR SEPARATED USE, THE
 ASSEMBLY OCCUPANCY WOULD REQUIRE TWO EXITS AND NEED TO
 BE SEPARATED FROM BUSINESS USE WITH A ONE HOUR FIRE
 BARRIER. FOR MIXED USE, THE BUILDING OCCUPANT LOAD
 EXCEEDS 100 PERSONS AND WOULD REQUIRE EXIT DOORS TO BE
 EQUIPPED WITH PANIC HARDWARE AND WOULD NOT ALLOW THE
 USE OF A THUMB TURN LOCK.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW