| 2011-06-29 11:55:15 | 1507 BELVEDERE ROAD |
| | PERMIT #11060444 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | STRUCTURES WITH LIGHT FRAME ROOF TRUSS CONSTRUCTION |
| | SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO THE |
| | BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| | REFLECTIVE COLOR AND BEAR THE LETTER R DESIGNATION PER |
| | FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE CODE |
| | 69A-60.0081. |
| | |
| | PORTABLE FIRE EXTINGUISHERS SHOWN IN CABINETS SHALL |
| | HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE TAGGED BY |
| | A LICENSED FIRE EXTINGUISHER COMPANY. |
| | |
| | PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. |
| | NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND |
| | SHALL CONTRAST THE BACKGROUND. |
| | |
| | THE OCCUPANCY IS LISTED AS BUSINESS; HOWEVER, THE |
| | BUILDING IS FUNCTIONING AS A MULTI-USE (BUSINESS AND |
| | ASSEMBLY) OCCUPANCY. THE BUILDING DESIGN SHALL CONFORM |
| | TO THE REQUIREMENTS FOR MIXED USE (NON-SEPARATED) OR |
| | SEPARATED USE AS INDICATED IN SECTION 6.1.14.2 OF NFPA |
| | 101 FLORIDA EDITION 2006. FOR SEPARATED USE, THE |
| | ASSEMBLY OCCUPANCY WOULD REQUIRE TWO EXITS AND NEED TO |
| | BE SEPARATED FROM BUSINESS USE WITH A ONE HOUR FIRE |
| | BARRIER. FOR MIXED USE, THE BUILDING OCCUPANT LOAD |
| | EXCEEDS 100 PERSONS AND WOULD REQUIRE EXIT DOORS TO BE |
| | EQUIPPED WITH PANIC HARDWARE AND WOULD NOT ALLOW THE |
| | USE OF A THUMB TURN LOCK. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |