| Plan Review Notes For Permit 11060376 |
| Permit Number |
11060376 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-06-24 15:15:34 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. AN ATRIUM IS SHOWN ON THE PLAN. PLEASE SEE FBC 404. | | | THE PLANS SHOULD SHOW HOW THE ATRIUM AND ASSOCIATED | | | SPRINKLERS, SMOKE CONTROL SYSTEM, ETC. ARE AFFECTED. | | | | | | 2. PLEASE SEE FBC1609, EITHER REVISE TO EXPOSURE C OR | | | PROVIDE RATIONAL ANALYSIS CALCULATIONS FOR USE OF | | | REDUCED PRESSURES IN THE TRANSITION ZONE. | | | | | | |
|