| 2011-06-20 15:31:39 | 2007 FBC W/2009 REVISIONS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) SPECIFY THE DESIGN CRITERIA ON THE PLANS PER FBC R |
| | 301. THE WINDSPEED IS 140 MPH AND THE EXPOSURE CATEGORY |
| | IS B. |
| | |
| | 2) PROVIDE THE ROOF SCUPPER AND SECONDARY SCUPPER |
| | SIZING CALCULATIONS IN ACCORDANCE WITH FBC PLUMBING |
| | 1106.7 AND 1107. INCLUDE HALF THE VERTICAL WALL AREA OF |
| | THE PARAPET WALL WITH THE ROOF AREA PER FBC R 1106.4. |
| | FBC R1107.3 STATES THAT SCUPPERS SHOULD NOT HAVE AN |
| | OPENING DIMENSION OF LESS THAN 4 INCHES. |
| | |
| | 3) SHOW COMPLIANCE WITH FBC R 313.4 WHICH REQUIRES A |
| | CARBON MONOXIDE DETECTOR WITHIN 10 FEET OF EACH ROOM |
| | USED FOR SLEEPING PURPOSES. |
| | |
| | 4) SHOW COMPLIANCE WITH FBC R 320 FOR TERMITE |
| | PROTECTION. |
| | |
| | 5) SHOW COMPLIANCE WITH FBC R320.7 FOR THE SCUPPERS TO |
| | EMPTY INTO DOWNSPOUTS THAT DISCHARGE AT LEAST ONE FOOT |
| | FROM THE STRUCTURE SIDE WALL. |
| | |
| | 6) SHOW COMPLIANCE WITH FBC R 703.6.3 WHICH REQUIRES A |
| | BOND BREAK BETWEEN THE EXTERIOR STUCCO AND THE |
| | WATER-RESISTIVE BARRIER. |
| | |
| | 7) SHOW COMPLIANCE WITH FBC R 803.2.3.1 WHICH REQUIRES |
| | 8D RING SHANK NAILS FOR FASTENING THE ROOF SHEATHING. |
| | (SHEET 2) |
| | |
| | 8) SHOW COMPLIANCE WITH FBC R 408.1 UNDER FLOOR SPACE |
| | VENTILATION AND R408.4 ACCESS TO UNDER FLOOR SPACE. |
| | |
| | 9) SHOW COMPLIANCE WITH FBC R 806.1 FOR ATTIC |
| | VENTILATION AND R 807.1 FOR ATTIC ACCESS. |
| | |