Plan Review Notes
Plan Review Notes For Permit 11060364
Permit Number 11060364
Review Stop B
Sequence Number 1
Notes
Date Text
2011-06-20 15:31:392007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SPECIFY THE DESIGN CRITERIA ON THE PLANS PER FBC R
 301. THE WINDSPEED IS 140 MPH AND THE EXPOSURE CATEGORY
 IS B.
  
 2) PROVIDE THE ROOF SCUPPER AND SECONDARY SCUPPER
 SIZING CALCULATIONS IN ACCORDANCE WITH FBC PLUMBING
 1106.7 AND 1107. INCLUDE HALF THE VERTICAL WALL AREA OF
 THE PARAPET WALL WITH THE ROOF AREA PER FBC R 1106.4.
 FBC R1107.3 STATES THAT SCUPPERS SHOULD NOT HAVE AN
 OPENING DIMENSION OF LESS THAN 4 INCHES.
  
 3) SHOW COMPLIANCE WITH FBC R 313.4 WHICH REQUIRES A
 CARBON MONOXIDE DETECTOR WITHIN 10 FEET OF EACH ROOM
 USED FOR SLEEPING PURPOSES.
  
 4) SHOW COMPLIANCE WITH FBC R 320 FOR TERMITE
 PROTECTION.
  
 5) SHOW COMPLIANCE WITH FBC R320.7 FOR THE SCUPPERS TO
 EMPTY INTO DOWNSPOUTS THAT DISCHARGE AT LEAST ONE FOOT
 FROM THE STRUCTURE SIDE WALL.
  
 6) SHOW COMPLIANCE WITH FBC R 703.6.3 WHICH REQUIRES A
 BOND BREAK BETWEEN THE EXTERIOR STUCCO AND THE
 WATER-RESISTIVE BARRIER.
  
 7) SHOW COMPLIANCE WITH FBC R 803.2.3.1 WHICH REQUIRES
 8D RING SHANK NAILS FOR FASTENING THE ROOF SHEATHING.
 (SHEET 2)
  
 8) SHOW COMPLIANCE WITH FBC R 408.1 UNDER FLOOR SPACE
 VENTILATION AND R408.4 ACCESS TO UNDER FLOOR SPACE.
  
 9) SHOW COMPLIANCE WITH FBC R 806.1 FOR ATTIC
 VENTILATION AND R 807.1 FOR ATTIC ACCESS.
  