Plan Review Notes
Plan Review Notes For Permit 11060346
Permit Number 11060346
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-06-24 12:46:52215 SOUTH OLIVE AVENUE, SUITE #100
 PERMIT #11060346
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION: NFPA 1 AND NFPA 101 - 2006 EDITION
 WITH FLORIDA AMENDMENTS.
  
 PROVIDE EMERGENCY LIGHTING AND EXIT SIGNS. NOTE: TWO
 PATHS OF EXIT ARE REQUIRED FOR EDUCATIONAL OCCUPANCIES.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND FIRE ALARM SYSTEM. NOTE: SPRINKLERS ARE
 NEEDED IN THE VAULT/STORAGE ROOM IF THEY DO NOT ALREADY
 EXIST.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  