Plan Review Notes
Plan Review Notes For Permit 11060317
Permit Number 11060317
Review Stop M
Sequence Number 1
Notes
Date Text
2011-10-11 15:23:22REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. ELEVATOR VENTILATION DUCTS SHALL BE ENCLOSED BY
 CONSTRUCTION HAVING NOT LESS THAN THE FIRE PROTECTION
 RATING REQUIRED FOR THE HOISTWAY (2 HOURS, IN THIS
 CASE) PER FBC-B 3004.2.
  
 2. NO DETAIL PROVIDED FOR ATTACHMENT OF NEW CONDENSING
 UNITS TO EXISTING ROOF CURB ON PAGE M5.1. SHOW HOW
 ATTACHMENT FOR WIND RESISTANCE IS TO BE ACHIEVED PER
 FBC-M 301.12.
  