| Plan Review Notes For Permit 11060317 |
| Permit Number |
11060317 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-10-11 15:23:22 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. ELEVATOR VENTILATION DUCTS SHALL BE ENCLOSED BY | | | CONSTRUCTION HAVING NOT LESS THAN THE FIRE PROTECTION | | | RATING REQUIRED FOR THE HOISTWAY (2 HOURS, IN THIS | | | CASE) PER FBC-B 3004.2. | | | | | | 2. NO DETAIL PROVIDED FOR ATTACHMENT OF NEW CONDENSING | | | UNITS TO EXISTING ROOF CURB ON PAGE M5.1. SHOW HOW | | | ATTACHMENT FOR WIND RESISTANCE IS TO BE ACHIEVED PER | | | FBC-M 301.12. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|