| 2011-07-07 13:46:04 | 777 SOUTH FLAGLER DRIVE | | | PERMIT #11060317 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | SHEET E-5 | | | 1) A NEW SMOKE DETECTOR IS PROVIDED IN THE ELEVATOR | | | LOBBY (SERVICE ELEVATOR) OF THE WEST TOWER; HOWEVER, NO | | | SMOKE DETECTOR WAS PROVIDED IN THE ELEVATOR LOBBY OF | | | THE EAST TOWER. | | | | | | 2) CLARIFY THE INTENT OF THE MAGNETIC DOOR HOLDERS TO | | | BE RELEASED VIA "OVERHEAD DOOR CLOSURE." | | | | | | 3) CLARIFY THE MEANING OF "CLASS A" FIRE ALARM. | | | | | | SHEET E-6 | | | 1) SECTION CALLED "NOTES" STATES IN THE EVENT OF A FIRE | | | ALARM, "THE PASSENGER ELEVATORS WILL RECALL AND | | | SHUTDOWN." ELEVATORS SHOULD ONLY BE AUTOMATICALLY | | | RECALLED IF A SMOKE DETECTOR HAS OPERATED IN THE | | | ELEVATOR LOBBY, ELEVATOR MACHINE ROOM, OR ELEVATOR | | | SHAFT. ELEVATOR POWER SHOULD ONLY BE SHUNTED BY A HEAT | | | DETECTOR LOCATED IN THE ELEVATOR SHAFT, OR A HEAT | | | DETECTOR/FLOW SWITCH LOCATED IN THE ELEVATOR MACHINE | | | ROOM. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|