2011-07-07 13:46:04777 SOUTH FLAGLER DRIVE
 PERMIT #11060317
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET E-5
 1) A NEW SMOKE DETECTOR IS PROVIDED IN THE ELEVATOR
 LOBBY (SERVICE ELEVATOR) OF THE WEST TOWER; HOWEVER, NO
 SMOKE DETECTOR WAS PROVIDED IN THE ELEVATOR LOBBY OF
 THE EAST TOWER.
  
 2) CLARIFY THE INTENT OF THE MAGNETIC DOOR HOLDERS TO
 BE RELEASED VIA "OVERHEAD DOOR CLOSURE."
  
 3) CLARIFY THE MEANING OF "CLASS A" FIRE ALARM.
  
 SHEET E-6
 1) SECTION CALLED "NOTES" STATES IN THE EVENT OF A FIRE
 ALARM, "THE PASSENGER ELEVATORS WILL RECALL AND
 SHUTDOWN." ELEVATORS SHOULD ONLY BE AUTOMATICALLY
 RECALLED IF A SMOKE DETECTOR HAS OPERATED IN THE
 ELEVATOR LOBBY, ELEVATOR MACHINE ROOM, OR ELEVATOR
 SHAFT. ELEVATOR POWER SHOULD ONLY BE SHUNTED BY A HEAT
 DETECTOR LOCATED IN THE ELEVATOR SHAFT, OR A HEAT
 DETECTOR/FLOW SWITCH LOCATED IN THE ELEVATOR MACHINE
 ROOM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW