Plan Review Notes
Plan Review Notes For Permit 11060299
Permit Number 11060299
Review Stop B
Sequence Number 1
Notes
Date Text
2011-07-06 14:56:17****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. FBC3501.3.5, PROVIDE DOCUMENTATION TO SHOW THAT THE
 FABRIC MEETS THE REQUIREMENT OF NFPA701.
  
 2. PROVIDE A SITE PLAN SHOWING LOCATION OF PROPOSED
 IMPROVEMENTS, FBC 106. PLEASE INCLUDE PROPOSED HEIGHT,
 INCLUDING HEIGHT AT LOWEST POINT IN THE OPEN POSITION.
 SEE FBC 1003, FBC11-4.4, FBC3202. NOT ENOUGH
 INFORMATION HAS BEEN PROVIDED TO PROVIDE A MORE
 ACCURATE CHECKLIST. THE SITE PLAN SHOULD CLEARLY SHOW
 HOW ACCESSIBLE ROUTE AND EXIT DISCHARGE WILL BE
 AFFECTED.
  
 3. PROVIDE AN ENGINEERED DETAIL TO SHOW HOW THE AWNING
 WILL RESIST WIND LOADS IN THE CLOSED POSITION, FBC1609.
 THE ENGINEERING PROVIDED IS A DETAIL OF THE AWNING
 CONSTRUCTION, BUT DOES NOT INCLUDE ATTACHMENT
 INFORMATION (HOW THE AWNING WILL ATTACH TO THE
 BUILDING), WIND DESIGN CRITERIA FBC1603.1.4 (WIND ZONE,
 EXPOSURE, AND WIND PRESSURES), AND IS NOT SIGNED AND
 SEALED AS REQUIRED BY FS471.
  
  