| Plan Review Notes For Permit 11060299 |
| Permit Number |
11060299 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-07-06 14:56:17 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. FBC3501.3.5, PROVIDE DOCUMENTATION TO SHOW THAT THE | | | FABRIC MEETS THE REQUIREMENT OF NFPA701. | | | | | | 2. PROVIDE A SITE PLAN SHOWING LOCATION OF PROPOSED | | | IMPROVEMENTS, FBC 106. PLEASE INCLUDE PROPOSED HEIGHT, | | | INCLUDING HEIGHT AT LOWEST POINT IN THE OPEN POSITION. | | | SEE FBC 1003, FBC11-4.4, FBC3202. NOT ENOUGH | | | INFORMATION HAS BEEN PROVIDED TO PROVIDE A MORE | | | ACCURATE CHECKLIST. THE SITE PLAN SHOULD CLEARLY SHOW | | | HOW ACCESSIBLE ROUTE AND EXIT DISCHARGE WILL BE | | | AFFECTED. | | | | | | 3. PROVIDE AN ENGINEERED DETAIL TO SHOW HOW THE AWNING | | | WILL RESIST WIND LOADS IN THE CLOSED POSITION, FBC1609. | | | THE ENGINEERING PROVIDED IS A DETAIL OF THE AWNING | | | CONSTRUCTION, BUT DOES NOT INCLUDE ATTACHMENT | | | INFORMATION (HOW THE AWNING WILL ATTACH TO THE | | | BUILDING), WIND DESIGN CRITERIA FBC1603.1.4 (WIND ZONE, | | | EXPOSURE, AND WIND PRESSURES), AND IS NOT SIGNED AND | | | SEALED AS REQUIRED BY FS471. | | | | | | |
|