| Notes |
| Date |
Text |
| 2011-06-30 16:04:00 | 2009 FBC W/2009 REVISIONS | | | | | | DENIED BY PLUMBING | | | | | | 1) SUBMIT TWO SETS OF TDH CALCULATIONS FOR THE SYSTEM. | | | THE PUMP CURVE FOR THE HAYWARD SPP3010X15AZ PUMP | | | SPECIFIED ON THE PLANS HAS A MAXIMUM FLOW RATE OF 100 | | | GPM. WHEN TDH CALCULATIONS ARE NOT SUBMITTED THE | | | MAXIMUM FLOW RATE IS USED TO DETERMINE THE WATER | | | VELOCITY. AT 100 GPM THE WATER VELOCITY IN 2-1/2" PIPE | | | IS 6.54 FEET PER SECOND AND EXCEEDS THE 6 FEET PER | | | SECOND ALLOWED IN THE BRANCH SUCTION PIPING AT THE TWO | | | MAIN DRAINS. PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|