2011-06-23 09:51:03BUILDING PLAN REVIEW
 PERMIT: 11060245
 ADD: 2101 45TH ST
 CONT: HODGEN CONSTRUCTION & DEVELOPMENT
 TEL: (954) 895-1893
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
 1) SHEET A100 THE BUILDING DESIGN CRITERIA IS BLANK.
 PLEASE PROVIDE THE MINIMUM BUILDING TYPE THIS BUILDING
 CAN BE DESIGNED TO SINCE IT MAY EFFECT THE DESIGN
 COMPONENTS AND OR MATERIALS TO BE INSTALLED WITHIN OR
 ATTACHED TO THE STRUCTURE, TABLE 503 & CHAPTER 6.
  
 2) SHEET A302 & A700 BOTH INDICATE THE USE OF NEW
 EXTERIOR AUTOMATIC DOORS AS WELL AS STOREFRONT SYSTEMS.
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE
 AS FOLLOWS:
  
 2A) AUTOMATIC SLIDING DOORS
  
 2B) STOREFRONT SYSTEMS
  
 2C) MULLIONS- IF NOT PART OF THE PRODUCT APPROVAL
 PACKAGE
  
 2D) STORM SHUTTERS IF THE GLAZED AREAS BEING REPLACED
 DO NOT HAVE LARGE MISSILE IMPACT RESISTANCE TESTING
  
 2E) MCM PANELS
  
 3) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 4) AUTOMATIC HORIZONTAL SLIDING DOORS SHALL ALSO COMPLY
 WITH 1008.1.3.3 PLEASE PROVIDE PRODUCT SPECIFICATIONS.
 1008.1.3.3 HORIZONTAL SLIDING DOORS. IN OTHER THAN
 GROUP H OCCUPANCIES, HORIZONTAL SLIDING DOORS PERMITTED
 TO BE A COMPONENT OF A MEANS OF EGRESS IN ACCORDANCE
 WITH EXCEPTION 6 TO SECTION 1008.1.2 SHALL COMPLY WITH
 ALL OF THE FOLLOWING CRITERIA:
  
 1. THE DOORS SHALL BE POWER OPERATED AND SHALL BE
 CAPABLE OF BEING OPERATED MANUALLY IN THE EVENT OF
 POWER FAILURE.
  
 2. THE DOORS SHALL BE OPENABLE BY A SIMPLE METHOD FROM
 BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR EFFORT.
  
 3. THE FORCE REQUIRED TO OPERATE THE DOOR SHALL NOT
 EXCEED 30 POUNDS (133 N) TO SET THE DOOR IN MOTION AND
 15 POUNDS (67 N) TO CLOSE THE DOOR OR OPEN IT TO THE
 MINIMUM REQUIRED WIDTH.
  
 4. THE DOOR SHALL BE OPENABLE WITH A FORCE NOT TO
 EXCEED 15 POUNDS (67 N) WHEN A FORCE OF 250 POUNDS
 (1100 N) IS APPLIED PERPENDICULAR TO THE DOOR ADJACENT
 TO THE OPERATING DEVICE.
  
 5. THE DOOR ASSEMBLY SHALL COMPLY WITH THE APPLICABLE
 FIRE PROTECTION RATING AND, WHERE RATED, SHALL BE
 SELF-CLOSING OR AUTOMATIC-CLOSING BY SMOKE DETECTION,
 SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 80 AND SHALL
 COMPLY WITH SECTION 715.
  
 6. THE DOOR ASSEMBLY SHALL HAVE AN INTEGRATED STANDBY
 POWER SUPPLY.
  
 7. THE DOOR ASSEMBLY POWER SUPPLY SHALL BE ELECTRICALLY
 SUPERVISED.
  
 8. THE DOOR SHALL OPEN TO THE MINIMUM REQUIRED WIDTH
 WITHIN 10 SECONDS AFTER ACTIVATION OF THE OPERATING
 DEVICE.
  
 9. IN APARTMENT BUILDINGS, HOTELS AND DORMITORIES,
 HORIZONTAL SLIDING DOORS SHALL NOT BE USED ACROSS
 CORRIDORS
  
  
 5). PLEASE PROVIDE DOCUMENTATION FOR MCM PANELS FOR THE
 FOLLOWING:1407.2 EXTERIOR WALL FINISH. MCM USED AS
 EXTERIOR WALL FINISH OR AS ELEMENTS OF BALCONIES AND
 SIMILAR PROJECTIONS AND BAY AND ORIEL WINDOWS TO
 PROVIDE CLADDING OR WEATHER RESISTANCE SHALL COMPLY
 WITH SECTIONS 1407.4 THROUGH 1407.13.
  
 5A)1407.4 STRUCTURAL DESIGN. MCM SYSTEMS SHALL BE
 DESIGNED AND CONSTRUCTED TO RESIST WIND LOADS AS
 REQUIRED BY CHAPTER 16 FOR COMPONENTS AND CLADDING.
  
 5B) 1407.5 APPROVAL. RESULTS OF APPROVED TESTS OR AN
 ENGINEERING ANALYSIS SHALL BE SUBMITTED TO THE BUILDING
 OFFICIAL TO VERIFY COMPLIANCE WITH THE REQUIREMENTS OF
 CHAPTER 16 FOR WIND LOADS.
  
 5C) 1407.6 WEATHER RESISTANCE. MCM SYSTEMS SHALL COMPLY
 WITH SECTION 1403 AND SHALL BE DESIGNED AND CONSTRUCTED
 TO RESIST WIND AND RAIN IN ACCORDANCE WITH THIS SECTION
 AND THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
  
 5D) 1407.7 DURABILITY. MCM SYSTEMS SHALL BE CONSTRUCTED
 OF APPROVED MATERIALS THAT MAINTAIN THE PERFORMANCE
 CHARACTERISTICS REQUIRED IN SECTION 1407 FOR THE
 DURATION OF USE.
  
 5E) 1407.8 FIRE-RESISTANCE RATING. WHERE MCM SYSTEMS
 ARE USED ON EXTERIOR WALLS REQUIRED TO HAVE A
 FIRE-RESISTANCE RATING IN ACCORDANCE WITH SECTION 704,
 EVIDENCE SHALL BE SUBMITTED TO THE BUILDING OFFICIAL
 THAT THE REQUIRED FIRE-RESISTANCE RATING IS MAINTAINED.
  
 5F) 1407.9 SURFACE-BURNING CHARACTERISTICS. UNLESS
 OTHERWISE SPECIFIED, MCM SHALL HAVE A FLAME SPREAD
 INDEX OF 75 OR LESS AND A SMOKE-DEVELOPED INDEX OF 450
 OR LESS WHEN TESTED AS AN ASSEMBLY IN THE MAXIMUM
 THICKNESS INTENDED FOR USE IN ACCORDANCE WITH ASTM E
 84.
  
 5F) 1407.10 TYPE I, II, III AND IV CONSTRUCTION. WHERE
 INSTALLED ON BUILDINGS OF TYPE I, II, III AND IV
 CONSTRUCTION, MCM SYSTEMS SHALL COMPLY WITH SECTIONS
 1407.10.1 THROUGH 1407.10.4, OR 1407.11.
  
 5G) 1407.12 TYPE V CONSTRUCTION. MCM SHALL BE PERMITTED
 TO BE INSTALLED ON BUILDINGS OF TYPE V CONSTRUCTION.
  
 5H) 1407.13 LABELING. MCM SHALL BE LABELED IN
 ACCORDANCE WITH SECTION 1703.5.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  