| 2011-06-27 14:50:33 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. SCOPE NOT CLEAR. A BAHAMA SHUTTER IS SHOWN OVER THE |
| | DOOR. BASED ON TRAVEL DISTANCE AND DEAD END CREATED, |
| | THE EXIT DOOR CANNOT BE COVERED WITH A BAHAMA SHUTTER |
| | AS DEPICTED. |
| | |
| | FBC 1003.6, MEANS OF EGRESS CONTINUITY. THE PATH OF |
| | EGRESS TRAVEL ALONG A MEANS OF EGRESS SHALL NOT BE |
| | INTERRUPTED BY ANY BUILDING ELEMENT OTHER THAN A MEANS |
| | OF EGRESS COMPONENT AS SPECIFIED IN THIS CHAPTER. |
| | OBSTRUCTIONS SHALL NOT BE PLACED IN THE REQUIRED WIDTH |
| | OF A MEANS OF EGRESS EXCEPT PROJECTIONS PERMITTED BY |
| | THIS CHAPTER. |
| | |
| | 1008.1.3.5 SECURITY GRILLS. IN GROUPS B, F, M, R AND S, |
| | HORIZONTAL SLIDING OR VERTICAL SECURITY GRILLES ARE |
| | PERMITTED AT THE MAIN EXIT AND SHALL BE OPENABLE FROM |
| | THE INSIDE WITHOUT THE USE OF A KEY OR SPECIAL |
| | KNOWLEDGE OR EFFORT DURING PERIODS THAT THE SPACE IS |
| | OCCUPIED. THE GRILLES SHALL REMAIN SECURED IN THE |
| | FULL-OPEN POSITION DURING THE PERIOD OF OCCUPANCY BY |
| | THE GENERAL PUBLIC. WHERE TWO OR MORE MEANS OF EGRESS |
| | ARE REQUIRED, NOT MORE THAN ONE-HALF OF THE EXITS OR |
| | EXIT ACCESS DOORWAYS SHALL BE EQUIPPED WITH HORIZONTAL |
| | SLIDING OR VERTICAL SECURITY GRILLES. |
| | |
| | |