| 2011-06-10 10:24:20 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. THIS BUILDING EXCEEDS 3 STORIES, OUTSIDE SCOPE FOR | | | CBC, SEE FS489. THE COMPONENTS & CLADDING ARE SUBJECT | | | TO WIND LOADS. | | | | | | 2. DESIGN PRESSURES FOR BUILDINGS OVER 60FEET ARE | | | REQUIRED TO BE DESIGNED USING ASCE7, FBC1609.1.1. | | | DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR | | | PUBLIC RECORD ARE TO BE SIGNED SEALED ORIGINALS | | | FAC61G15-23.002. |
|