| Notes |
| Date |
Text |
| 2011-06-06 11:15:40 | PROVISO, PASS (PARTIAL) | | | | | | DOOR PRODUCT APPROVAL EXPIRED AND INCOMPLETE, PROVIDE | | | COMPLETE CURRENT PRODUCT APPROVAL FOR DOORS | | | | | | REVISED SHEET A2 | | | | | | DENIED SHEETS: | | | | | | 1. SUSPENDED LIGHT FIXTURE DETAIL - DELEGATED | | | ENGINEERING TO BE REVIEWED BY DESIGNER OF RECORD, | | | FAC61G15. | | | | | | 2. PLUMBING AS-BUILT CHANGES ARE TO BE INCORPORATED | | | INTO THE PLAN. THE PLUMBING CONTRACTOR CANNOT REVISE | | | THE DESIGNER OF RECORD'S PLAN. | | | | | | 3. MIAMI DADE NOA FOR DOORS IS INCOMPLETE AND EXPIRED, | | | PLEASE SUBMIT CURRENT APPROVALS. | | | | | | DENIED SHEETS ROUTED TO FRONT COUNTER FOR CONTRACTOR | | | PICKUP | | | |
|