 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE COMMUNICATING SPACE OF LOBBY #200 SHOWS CLOSELY
 SPACED SPRINKLERS PROTECTING THE GLASS CURTAIN WALL;
 THIS DESIGN ALTERNATIVE IS ONLY PERMITTED FOR ATRIUM
 FIRE SEPARATION.
  
 STORAGE #215 SHOWS A COUPLE SPRINKLERS SPACED 16 FEET
 APART.
  
 STORAGE LEDGER #301 SHOWS SPRINKLERS PROTECTING MORE
 THAN 130 SQUARE FEET.
  
 REPEAT COMMENT: PROVIDE LOCKABLE KNOX CAPS ON EXISTING
 FIRE DEPARTMENT CONNECTION. CAPS CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 REPEAT COMMENT: PROVIDE RECENT FIRE HYDRANT FLOW TEST
 DATA ON PLANS.
  
 NOTE: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE
 DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE
 EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR
 MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING
 SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH
 REQUESTS MUST BE APPROVED AND SUBMITTED IN WRITING TO
 THE OFFICE OF THE FIRE MARSHAL.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  