| Plan Review Notes For Permit 11060099 |
| Permit Number |
11060099 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-08-03 12:29:13 | 201 CLEMATIS STREET | | | PERMIT #11060099 | | | MASTER #11030136 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE COMMUNICATING SPACE OF LOBBY #200 SHOWS CLOSELY | | | SPACED SPRINKLERS PROTECTING THE GLASS CURTAIN WALL; | | | THIS DESIGN ALTERNATIVE IS ONLY PERMITTED FOR ATRIUM | | | FIRE SEPARATION. | | | | | | STORAGE #215 SHOWS A COUPLE SPRINKLERS SPACED 16 FEET | | | APART. | | | | | | STORAGE LEDGER #301 SHOWS SPRINKLERS PROTECTING MORE | | | THAN 130 SQUARE FEET. | | | | | | REPEAT COMMENT: PROVIDE LOCKABLE KNOX CAPS ON EXISTING | | | FIRE DEPARTMENT CONNECTION. CAPS CAN BE ORDERED FROM | | | WWW.KNOXBOX.COM. | | | | | | REPEAT COMMENT: PROVIDE RECENT FIRE HYDRANT FLOW TEST | | | DATA ON PLANS. | | | | | | NOTE: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE | | | DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE | | | EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR | | | MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING | | | SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH | | | REQUESTS MUST BE APPROVED AND SUBMITTED IN WRITING TO | | | THE OFFICE OF THE FIRE MARSHAL. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|