2011-06-07 17:14:48201 CLEMATIS STREET
 PERMIT #11060099
 MASTER #11030136
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE JOB VALUE AND SCOPE OF SPRINKLER WORK DOES NOT
 CORRESPOND WITH THE AMOUNT OF RENOVATIONS OCCURING AT
 THE FACILITY. FOR EXAMPLE THE ARCHITECTURAL SHEETS SHOW
 SEVERAL CEILINGS THAT ARE BEING ALTERED OR REPLACED;
 HOWEVER, THE SPRINKLER SCOPE DOES NOT SEEM TO ACCOUNT
 FOR THESE SPACES. ENGINEERING SHEET FP1.01 INDICATES
 THE 1-1/2" SPRINKLER LOOP TO BE RAISED TIGHT TO
 STRUCTURE AND NEW SPRINKLERS TO BE LOCATED UNDER THE
 NEW CANOPY ETC. REAR STAIR NUMBER 12 IS A NEW STAIR.
  
 PROVIDE LOCKABLE KNOX CAPS ON EXISTING FIRE DEPARTMENT
 CONNECTION. CAPS CAN BE ORDERED FROM WWW.KNOXBOX.COM.
  
 PROVIDE RECENT FIRE HYDRANT FLOW TEST DATA ON PLANS.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF
 THE FIRE MARSHAL.
  
 CLOSELY SPACED SPRINKLERS AND 18-INCH DEEP DRAFTSTOPS
 ARE REQUIRED AROUND THE ENTRANCE LOBBY FLOOR OPENING.
  
 IDENTIFY SIZE OF STAGE AS STAGES GREATER THAN 1,000
 SQUARE FEET REQUIRE FIRE DEPARTMENT HOSE VALVES.
  
 COSTUME AND STORAGE SPACES SHALL BE DESIGNED AS
 ORDINARY HAZARD DUE TO THE INCREASED FIRE LOAD.
  
 SPRINKLER IN CONFERENCE ROOM 118 IS MORE THAN 9' FROM
 WALL.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  