| 2011-07-18 08:52:07 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW SECOND | | | CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- ENGINEER LETTER FROM HUSTAD STRUCTURAL ENGINEERING | | | NEEDS TO BE SIGNED AND SEALED BY THE ENGINEER AS | | | REQUIRED BY CHAPTER 471 FLORIDA STATUTES. LETTER | | | PROVIDED IS NOT SIGNED AND SEALED. | | | PROVIDE 2 COPIES WITH ORIGINAL SEAL AND SIGNATURE. ONLY | | | ONE COPY WITHOUT SEAL AND SIGNATURE WAS SUBMITTED. | | | | | | 2- FLAT ROOF NOA 07-1203.01 SUBMITTED WAS SUPERSEDED. | | | (REPEAT COMMENT). ENGINEER DOING THE RAS 117 | | | CALCULATIONS IS REFERENCING THIS NOA. ENGINEER NEEDS TO | | | REVISE THE RAS 117 CALCULATIONS USING A CURRENT NOA. | | | PROVIDE 2 COPIES OF RAS 117 CALCULATIONS ONLY ONE WAS | | | PROVIDED. | | | | | | 3- PROVIDE TWO COPIES OF POLYFOAM NOA. ONLY ONE COPY | | | WAS SUBMITTED. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|