2011-06-02 08:54:09RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ACCORDING TO CITY RECORDS PERMIT #99081115 AND
 PROPERTY APPRAISAL RECORDS THIS HOUSE ROOF COVER IS
 ASPHALT SHINGLES. PROPOSED ROOF COVER IS CONCRETE TILE.
 NEED TO PROVIDE ENGINEERING SHOWING THAT THE EXISTING
 STRUCTURE IS DESIGNED TO RESIST THE ADDITIONAL LOAD.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC.
  
 2- FLAT ROOF PRODUCT APPROVAL SUBMITTED:
 A) NOA 07-1203.01 SUBMITTED WAS SUPERSEDED BY
 MIAMI-DADE. VISIT MIAMI-DADE WEBSITE DOWNLOAD CURRENT
 NOA AND RESUBMIT.
  
 B) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.
  
 C) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION # 7 ON LAST PAGE OF NOA.
 ***NOTE: ASSEMBLIES THAT ARE LIMITED BY GENERAL
 LIMITATION #9 CAN'T BE USED IN THIS BUILDING BECAUSE
 THEY DON'T MEET THE DESIGN PRESSURES REQUIRED BY SEC.
 R301.
  
 D) DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS
 TO TAKE INTO CONSIDERATION THAT ACCORDING TO THE 2009
 REVISIONS SEC. R301.2.1.4.3 THS BUILDING IS LOCATED ON
 EXPOSURE "C".
  
 3- CONCRETE TILE NOA 07-1018.08 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. VISIT MIAMI-DADE WEBSITE
 DOWNLOAD CURRENT NOA AND RESUBMIT.
  
 4- POLYFOAM NOA 06-0201.02 SUBMITTED EXPIRED ON
 05/10/11. PROVIDE CURRENT NOA.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712