| 2011-06-02 08:54:09 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- ACCORDING TO CITY RECORDS PERMIT #99081115 AND |
| | PROPERTY APPRAISAL RECORDS THIS HOUSE ROOF COVER IS |
| | ASPHALT SHINGLES. PROPOSED ROOF COVER IS CONCRETE TILE. |
| | NEED TO PROVIDE ENGINEERING SHOWING THAT THE EXISTING |
| | STRUCTURE IS DESIGNED TO RESIST THE ADDITIONAL LOAD. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 2- FLAT ROOF PRODUCT APPROVAL SUBMITTED: |
| | A) NOA 07-1203.01 SUBMITTED WAS SUPERSEDED BY |
| | MIAMI-DADE. VISIT MIAMI-DADE WEBSITE DOWNLOAD CURRENT |
| | NOA AND RESUBMIT. |
| | |
| | B) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO |
| | BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301. |
| | |
| | C) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR |
| | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS |
| | REQUIRED BY GENERAL LIMITATION # 7 ON LAST PAGE OF NOA. |
| | ***NOTE: ASSEMBLIES THAT ARE LIMITED BY GENERAL |
| | LIMITATION #9 CAN'T BE USED IN THIS BUILDING BECAUSE |
| | THEY DON'T MEET THE DESIGN PRESSURES REQUIRED BY SEC. |
| | R301. |
| | |
| | D) DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS |
| | TO TAKE INTO CONSIDERATION THAT ACCORDING TO THE 2009 |
| | REVISIONS SEC. R301.2.1.4.3 THS BUILDING IS LOCATED ON |
| | EXPOSURE "C". |
| | |
| | 3- CONCRETE TILE NOA 07-1018.08 SUBMITTED WAS |
| | SUPERSEDED BY MIAMI-DADE. VISIT MIAMI-DADE WEBSITE |
| | DOWNLOAD CURRENT NOA AND RESUBMIT. |
| | |
| | 4- POLYFOAM NOA 06-0201.02 SUBMITTED EXPIRED ON |
| | 05/10/11. PROVIDE CURRENT NOA. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |