Plan Review Notes
Plan Review Notes For Permit 11050822
Permit Number 11050822
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-06-10 13:46:50225 CLEMATIS STREET, SUITE #200
 PERMIT #11050822
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION: NFPA 1 AND NFPA 101 - 2006 EDITION
 WITH FLORIDA AMENDMENTS.
  
 PROVIDE ADDRESS SUITE NUMBER ON PLANS.
  
 INDICATE THE PREVIOUS OCCUPANCY/USE OF THIS SPACE.
 INDICATE IF ANY DEMOLITION WORK WILL BE PERFORMED.
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF
 THE FIRE MARSHAL.
  
 THIS SPACE IS FUNCTIONING AS AN ASSEMBLY OCCUPANCY NOT
 A BUSINESS OCCUPANCY. OCCUPANT LOAD SHOULD BE BASED
 UPON 15 SQ.FT. PER PERSON PER NFPA 101 TABLE 7.3.1.2.
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER?PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA
 FIRE PREVENTION CODE ? NFPA 101
  
 THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE
 DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA
 EDITION 2007. PANIC OR FIRE EXIT HARDWARE REQUIRED FOR
 ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING
 100 PERSONS.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PORTABLE FIRE EXTINGUISHERS SHALL HAVE A MINIMUM RATING
 OF 2A:10BC AND SHALL BE TAGGED BY A LICENSED FIRE
 EXTINGUISHER COMPANY.
  
 SHEET FA1.01: NOTIFICATION SIGNALS FOR OCCUPANTS TO
 EVACUATE SHALL BE AUDIBLE AND VISIBLE SIGNALS IN
 ACCORDANCE WITH NFPA 72. CURRENTLY ONLY STROBE DEVICES
 HAVE BEEN PROVIDED FOR THE STUDIO AND OFFICE SPACES.
  
 SHEET FA1.01: PER LOCAL CODE AMENDMENTS, DUCT SMOKE
 DETECTORS SHALL INITIATE A GENERAL FIRE ALARM
 CONDITION.
  
 VERIFY TOTAL SPRINKLER SCOPE DOES NOT AFFECT 50 OR MORE
 SPRINKLERS, AS SECTION 105.3.1.2(2) OF THE FLORIDA
 BUILDING CODE REQUIRES SEALED FIRE PROTECTION
 CONSTRUCTION DOCUMENTS FOR THE RELOCATION, ADDITION, OR
 DELETION OF 50 OR MORE AUTOMATIC FIRE SPRINKLERS.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 PLANS SHALL INDICATE THE HAZARD CLASSIFICATIONS, DESIGN
 DENSITIES, AND WATER SUPPLY DATA.
  
 USE OF FLEXIBLE DROPS IN LIEU OF STEEL PIPING WILL
 REQUIRE HYDRAULIC CALCULATIONS ACCOUNTING FOR THE
 ADDITIONAL FRICTION LOSS IN THIS MATERIAL. INDICATE
 MAXIMUM LENGTH OF FLEXIBLE DROPS TO BE USED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  