| 2011-06-10 15:18:06 | 314 3RD STREET | | | PERMIT #11050805 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | SHEET LP-3: FIRE HYDRANTS SHALL BE PROVIDED WITH | | | CLEARANCES OF 7?-6? TO THE FRONT/SIDES AND 4? TO THE | | | BACKSIDE PER SECTION 18.3.4.1 OF NFPA 1 FLORIDA | | | EDITION. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|