Plan Review Notes
Plan Review Notes For Permit 11050785
Permit Number 11050785
Review Stop B
Sequence Number 1
Notes
Date Text
2011-06-22 09:06:04BUILDING PLAN REVIEW
 PERMIT: 11050785
 ADD: ????????
 CONT:KAUFMAN & LYNN CONSTRUCTION
 TEL: (561) 361-6700
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE THE BUILDING DEPARTMENT WITH AN UPDATED
 CONTRACTOR OF RECORD, I HAD CONTACTED KAUFMAN & LYNN
 WITH QUESTIONS ONLY TO FIND OUT THEY ARE NO LONGER THE
 CONTRACTOR OF RECORD.
  
 2) PLEAS PROVIDE A KEY PLAN OF WHAT BUILDINGS ARE BEING
 MOVED TO WHICH SITES DO NOT USE ADRESES SINCE THE NEW
 ADRESES MAY CHANGE THEY WIL BE ASIGNED BY THE CITY.
  
 3) THE PLANS ARE NOT CLEAR AS TO WHAT WORK IS TO BE
 COVERED UNDER THIS PERMIT, (3) ADRESSES ARE INDICATED
 ON THE PERMIT APLICATION?
  
 4) STRUCTURAL SHET S-1 DOES NOT HAVE THE ADDRESS OF
 WHERE THE STRUCTURE IS BEING MOVED TO, THIS WOULD BE
 WHERE THE NEW FOUNDATION WIL BE LOCATED.
  
 5) S-1,PLEASE REVIEW THE NEW LOCATION WHERE THIS
 BUILDING IS BEING LOCATED, THE FOUNDATION NEDS TO
 REFLECT THIS LOCATION BEING LOCATED WITHIN A "C"
 COASTAL EXPOSURE PLEASE UPDATE PLANS.
 1609.4.3 EXPOSURE CATEGORIES. AN EXPOSURE CATEGORY
 SHALL BE DETERMINED IN ACCORDANCE WITH THE FOLLOWING:
  
 EXPOSURE C. OPEN TERRAIN WITH SCATTERED OBSTRUCTIONS,
 INCLUDING SURFACE UNDULATIONS OR OTHER IRREGULARITIES,
 HAVING HEIGHTS GENERALLY LESS THAN 30 FEET (9144 MM)
 EXTENDING MORE THAN 1,500 FEET (457.2 M) FROM THE
 BUILDING SITE IN ANY QUADRANT. THIS EXPOSURE SHALL ALSO
 APPLY TO ANY BUILDING LOCATED WITHIN EXPOSURE B-TYPE
 TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET
 HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF EXPOSURE
 C-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET (182.9
 M) AND WIDTH GREATER THAN 150 FT. IN THE UPWIND
 DIRECTION. SHORT-TERM (LESS THAN TWO YEAR) CHANGES IN
 THE PRE-EXISTING TERRAIN EXPOSURE, FOR THE PURPOSES OF
 DEVELOPMENT, SHALL NOT BE CONSIDERED OPEN FIELDS. WHERE
 DEVELOPMENT BUILDOUT WILL OCCUR WITHIN THREE YEARS AND
 THE RESULTANT CONDITION WILL MEET THE DEFINITION OF
 EXPOSURE B, EXPOSURE B SHALL BE REGULATING FOR THE
 PURPOSE OF PERMITTING. THIS CATEGORY INCLUDES FLAT OPEN
 COUNTRY, GRASSLANDS AND OCEAN OR GULF SHORELINES AND
 SHALL EXTEND DOWNWIND FOR A DISTANCE OF 1500 FEET. FOR
 BUILDINGS LOCATED WITHIN A DISTANCE OF 600 FEET OF
 INLAND BODIES OF WATER THAT PRESENT A FETCH OF 1 MILE
 (1.61 KM) OR MORE OR INLAND WATERWAYS OR RIVERS WITH A
 WIDTH OF 1 MILE (1.61 KM) OR MORE ROOF SHEATHING UPLIFT
 AND ROOF-TO-WALL UPLIFT LOADS SHALL BE INCREASED BY 20
 PERCENT.
  
 6) S-1 JURISDICTION IS NOT ST. LUCIE CTY, AND PROJECT
 NAME.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]