| Plan Review Notes For Permit 11050760 |
| Permit Number |
11050760 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-06-07 15:14:41 | 1411 NORTH FLAGLER DRIVE SUITE #9200 | | | PERMIT #11050760 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE ADDRESS ON THE PERMIT APPLICATION DOES NOT MATCH | | | THE ADDRESS ON THE PLANS. | | | | | | EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE | | | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING | | | FIRE/SMOKE BARRIER - PROTECT ALL OPENINGS. CHARACTERS | | | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN | | | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 | | | FEET ON CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA | | | FIRE PREVENTION CODE - NFPA 101. | | | | | | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS | | | OF NFPA 241. | | | | | | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING | | | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A | | | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN | | | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE | | | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST | | | BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF | | | THE FIRE MARSHAL. | | | | | | DRAWING INDICATES 5 POUND PORTABLE FIRE EXTINGUISHERS. | | | EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC | | | AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER | | | COMPANY. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|