2011-07-08 13:55:23525 SOUTH FLAGLER DRIVE - MEZZANINE
 PERMIT #11050759
 ROUND 3 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FOR ASSEMBLY OCCUPANCIES, THE COMMON PATH OF TRAVEL TO
 ONE MEANS OF EGRESS IS LIMITED TO 20 FEET WHEN THE
 OCCUPANT LOAD EXCEEDS 50 PERSONS PER SECTION 13.2.5.1.2
 OF NFPA 101 FLORIDA EDITION.
  
 IF NEW GLASS ENTRY DOORS ARE EQUIPPED WITH A LOCK OR
 LATCH, THESE DOORS ARE REQUIRED TO HAVE LISTED PANIC OR
 FIRE EXIT HARDWARE TO RELEASE THE LOCK/LATCH. POSTING A
 SIGN THAT THE DOORS ARE TO REMAIN UNLOCKED WHEN THE
 SPACE IS OCCUPIED IS ONLY ALLOWED FOR EXTERIOR DOORS
 PER SECTION 7.2.1.5.4 OF NFPA 101 FLORIDA EDITION.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW