| 2011-06-30 12:39:31 | 525 SOUTH FLAGLER DRIVE - MEZZANINE |
| | PERMIT #11050759 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | PER SECTION 13.2.4.7 OF NFPA 101 FLORIDA EDITION |
| | (2006), MEZZANINES WITH AN OCCUPANT LOAD GREATER |
| | THAN100 PERSONS SHALL HAVE TWO SEPARATE MEANS OF |
| | EGRESS. A COMMON PATH OF TRAVEL IS LIMITED TO 20 FEET |
| | WHEN THE OCCUPANT LOAD EXCEEDS 50 PERSONS. NOTE: TWO |
| | REMOTE MEANS OF EGRESS CAN LEAD TO THE FLOOR BELOW WHEN |
| | THE OCCUPANT LOAD DOES NOT EXCEED 100 PERSONS. |
| | |
| | IF NEW GLASS ENTRY DOORS (DOUBLE DOORS) ARE EQUIPPED |
| | WITH A LOCK OR LATCH, THESE DOORS ARE REQUIRED TO HAVE |
| | LISTED PANIC HARDWARE TO RELEASE THE LOCK/LATCH. |
| | |
| | PROVIDE EMERGENCY LIGHTING. ARCHITECTURAL AND |
| | ELECTRICAL SHEETS INDICATE "EMERGENCY LIGHT" WHILE |
| | POINTING TO AN EXIT SIGN. INDICATE IF THESE FIXTURES |
| | ARE COMBINATION EXIT SIGNS AND EMERGENCY LIGHTS WITH |
| | BATTERY BACK-UP. |
| | |
| | REPEAT COMMENT: INDICATE ON SHEET E-1 WHAT TYPE OF FIRE |
| | ALARM DEVICES ARE SHOWN. SHEET ONLY INDICATES THE |
| | LETTER "F" INSIDE A SQUARE. |
| | |
| | SCOPE OF WORK WILL AFFECT FIRE PROTECTION EQUIPMENT |
| | CONTRARY TO SHEET E-2. SPRINKLERS AND FIRE ALARM |
| | NOTIFICATION APPLIANCES WILL NEED TO BE ADDED TO |
| | ACCOMODATE THE ROOMS CREATED BY ADDING WALLS. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |