Plan Review Notes
Plan Review Notes For Permit 11050759
Permit Number 11050759
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2011-06-30 12:39:31525 SOUTH FLAGLER DRIVE - MEZZANINE
 PERMIT #11050759
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER SECTION 13.2.4.7 OF NFPA 101 FLORIDA EDITION
 (2006), MEZZANINES WITH AN OCCUPANT LOAD GREATER
 THAN100 PERSONS SHALL HAVE TWO SEPARATE MEANS OF
 EGRESS. A COMMON PATH OF TRAVEL IS LIMITED TO 20 FEET
 WHEN THE OCCUPANT LOAD EXCEEDS 50 PERSONS. NOTE: TWO
 REMOTE MEANS OF EGRESS CAN LEAD TO THE FLOOR BELOW WHEN
 THE OCCUPANT LOAD DOES NOT EXCEED 100 PERSONS.
  
 IF NEW GLASS ENTRY DOORS (DOUBLE DOORS) ARE EQUIPPED
 WITH A LOCK OR LATCH, THESE DOORS ARE REQUIRED TO HAVE
 LISTED PANIC HARDWARE TO RELEASE THE LOCK/LATCH.
  
 PROVIDE EMERGENCY LIGHTING. ARCHITECTURAL AND
 ELECTRICAL SHEETS INDICATE "EMERGENCY LIGHT" WHILE
 POINTING TO AN EXIT SIGN. INDICATE IF THESE FIXTURES
 ARE COMBINATION EXIT SIGNS AND EMERGENCY LIGHTS WITH
 BATTERY BACK-UP.
  
 REPEAT COMMENT: INDICATE ON SHEET E-1 WHAT TYPE OF FIRE
 ALARM DEVICES ARE SHOWN. SHEET ONLY INDICATES THE
 LETTER "F" INSIDE A SQUARE.
  
 SCOPE OF WORK WILL AFFECT FIRE PROTECTION EQUIPMENT
 CONTRARY TO SHEET E-2. SPRINKLERS AND FIRE ALARM
 NOTIFICATION APPLIANCES WILL NEED TO BE ADDED TO
 ACCOMODATE THE ROOMS CREATED BY ADDING WALLS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW