| 2011-06-30 13:38:38 | BUILDING PLAN REVIEW |
| | PERMIT: 11050759 |
| | ADD: 525 S FLAGLER DR SUITE# (MEZZANINE LEVEL) |
| | CONTRACTOR: CAMBRIDGE |
| | TEL: (561)248-5266 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-2 INDICATES THE REMOVAL OF A WALL THAT IS |
| | COMMON TO THE FIRST FLOOR. THE PLANS INDICATE THIS TO |
| | BE A MEZZANINE LEVEL, IT CAN NOT BE DETERMINED IF THIS |
| | IS A MEZZANINE OR A INTERMETANT STORY, 2ND FLOOR THAT |
| | MAY NOT BE COMMON TO THE REST OF THE BUILDING. THE |
| | SQUARE FOOTAGE OF THE MEZZANINE IS INDICATED AS 2566 SQ |
| | FT THE CLEAR OPEN AREA BENEATH THE MEZZANINE WITHOUT |
| | ANY WALLS WILL NEED TO BE 5132 SQ FT TO MEET THE |
| | DEFINITION OF MEZZANINE. |
| | PLEASE PROVIDE DOCUMENTATION.505.2 EXCEPTION # 2. |
| | |
| | 2) THE MEZZANINE IS SUPPOSE TO BE OPEN TO THE ROOM |
| | BELOW 505.4PLEASE INDICATE IF ANY OF THE EXEMPTIONS |
| | APPLY. |
| | |
| | 3) IF THIS AREA IS TO BE CONSIDERED AN INTERMETANT 2ND |
| | FLOOR THAT WILL BE LOOKING INTO A LOBBY TYPE ATRIUM |
| | WITH A GLASS WALL, THEN THE REQUIREMNTS OF ATRIUM WILL |
| | APPLY TO THE GLASS WALL PLEASE SEE 404.5 EXCEPTION # 1. |
| | |
| | 4) IF THIS IS TRUELY THE 2ND FLOOR IS THERE A THIRD |
| | FLOOR THAT IS COMMON TO THE ATRIUM THAT WOULD ENACT |
| | 404.4 SMOKE CONTROL. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |