| 2011-06-10 12:25:45 | 525 SOUTH FLAGLER DRIVE - MEZZANINE |
| | PERMIT #11050759 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | OVERALL PLAN INFORMATION IS INCOMPLETE TO PERFORM A |
| | THOROUGH REVIEW OF THE DRAWINGS. |
| | |
| | PROVIDE A LIFE SAFETY PLAN SHOWING TRAVEL DISTANCES TO |
| | EXITS, EXIT DOORS, EMERGENCY LIGHTS, FIRE ALARM |
| | DEVICES, FURNITURE LAYOUT, PORTABLE FIRE EXTINGUISHERS, |
| | OCCUPANT LOAD, FIRE-RATED WALLS ETC. |
| | |
| | IDENTIFY ROOM NAMES ON PLANS. INDICATE IF THESE ROOMS |
| | ARE A CHANGE OF USE. |
| | |
| | INDICATE WHICH FLOOR IS ASSOCIATED WITH THE MEZZANINE. |
| | |
| | DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION |
| | CODE 2007 EDITION: NFPA 1 AND NFPA 101 - 2006 EDITION |
| | WITH FLORIDA AMENDMENTS. |
| | |
| | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| | OF NFPA 241. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF |
| | THE FIRE MARSHAL. |
| | |
| | IF APPLICABLE, DOOR IS REQUIRED TO SWING IN THE |
| | DIRECTION OF EGRESS TRAVEL FOR AN OCCUPANT LOAD OF 50 |
| | OR GREATER PERSONS PER SECTION 7.2.1.4.2 OF THE FLORIDA |
| | FIRE PREVENTION CODE: NFPA 101 - LIFE SAFETY CODE. |
| | |
| | INDICATE ON SHEET E-1 WHAT TYPE OF FIRE ALARM DEVICES |
| | ARE SHOWN. |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |