Plan Review Notes
Plan Review Notes For Permit 11050759
Permit Number 11050759
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-06-10 12:25:45525 SOUTH FLAGLER DRIVE - MEZZANINE
 PERMIT #11050759
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 OVERALL PLAN INFORMATION IS INCOMPLETE TO PERFORM A
 THOROUGH REVIEW OF THE DRAWINGS.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING TRAVEL DISTANCES TO
 EXITS, EXIT DOORS, EMERGENCY LIGHTS, FIRE ALARM
 DEVICES, FURNITURE LAYOUT, PORTABLE FIRE EXTINGUISHERS,
 OCCUPANT LOAD, FIRE-RATED WALLS ETC.
  
 IDENTIFY ROOM NAMES ON PLANS. INDICATE IF THESE ROOMS
 ARE A CHANGE OF USE.
  
 INDICATE WHICH FLOOR IS ASSOCIATED WITH THE MEZZANINE.
  
 DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION: NFPA 1 AND NFPA 101 - 2006 EDITION
 WITH FLORIDA AMENDMENTS.
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF
 THE FIRE MARSHAL.
  
 IF APPLICABLE, DOOR IS REQUIRED TO SWING IN THE
 DIRECTION OF EGRESS TRAVEL FOR AN OCCUPANT LOAD OF 50
 OR GREATER PERSONS PER SECTION 7.2.1.4.2 OF THE FLORIDA
 FIRE PREVENTION CODE: NFPA 101 - LIFE SAFETY CODE.
  
 INDICATE ON SHEET E-1 WHAT TYPE OF FIRE ALARM DEVICES
 ARE SHOWN.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  