| Plan Review Notes For Permit 11050735 |
| Permit Number |
11050735 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-06-10 13:15:47 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. SEE OPENING 2 (AND ALL OTHER OPENINGS OVER 5' WHICH | | | PROPOSE A SILL INSTALLATION). 9.5" ANCHOR SPACING IS | | | HIGHLIGHTED ON THE PRODUCT APPROVAL, BUT 10" IS | | | PROPOSED FOR ANCHOR SPACING. PLEASE REVISE INSTALLATION | | | SCHEDULE TO BE COMPLIANT WITH THE REQUIREMENTS OF THE | | | PRODUCT APPROVAL. | | | | | | 2. OPENING 10, BOTTOM ANCHOR SPACING, WAS LEFT BLANK. | | | PLEASE REVISE. | | | |
|