| 2011-06-01 09:44:15 | ****CORRECTIONS**** |
| | REVISED 6/3 |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. APPLICATION IS FOR ACCORDION SHUTTERS, BUT |
| | INSTALLATION SCHEDULE IS FOR HORIZONTAL INSTALLATION |
| | (SEE 7TH COLUMN ON INSTALLATION SCHEDULE FORM COMPLETED |
| | BY CONTRACTOR). SPANS DO APPEAR, HOWEVER, TO CORRELATE |
| | WITH THE VERTICAL DIMENSION. |
| | |
| | 2. THE "SHUTTER MOUNTING CONNECTION TYPE" SHOULD STATE |
| | WHICH CONNECTION TYPES ARE PROPSED. SEE SHEET 10; |
| | NAMING CONVENTION FOR THIS PRODUCT APPROVAL WOULD BE |
| | WALL MOUNT 1 (W/1"), WALL MOUNT 3. |
| | |
| | 3. PLEASE NOTE THAT THE SUBSTRATE ON THE INSTALLATION |
| | SCHEDULE IS BLOCK, BUT WALL MOUNT 1 (HIGHLIGHTED) |
| | REQUIRES A CONCRETE SUBSTRATE. CBS HOUSES TYPICALLY |
| | HAVE A POURED CONCRETE TOP SUBSTRATE, BLOCK BOTTOM |
| | SUBSTRATE. |
| | |
| | 4. SPANS NOT CORRECT. SPAN CANNOT BE THE SAME AS |
| | OPENING SIZE DUE TO EDGE DISTANCE. SPAN SHOULD EQUAL |
| | BLADE LENGTH. |
| | |
| | 5 PLEASE PROVIDE TWO SETS WHEN RESUBMITTING. DUE TO |
| | WORK LOAD, DECREASED STAFF, AND INCREASED OFFICE |
| | DUTIES, IT IS VERY DIFFICULT TO PROVIDE CLERICAL |
| | SERVICES. FAILURE TO PROVIDE ALL DOCUMENTS REQUIRED MAY |
| | RESULT IN PERMIT ISSUANCE DELAYS. |
| | |