| Notes |
| Date |
Text |
| 2011-06-14 15:59:33 | PLANS DENIED | | | 1) PAGE M1 A OF THE PLANS PROVIDE FIRE DAMPERS IN 12X14 | | | EXHAUST DUCT AND 12X12 EXHAUST DUCT . | | | SECTION 607.5.1 2007 FBC (M) | | | 2) PROVIDE MANUFACTURE INSTALLATION INSTRUCTIONS FOR | | | PIZZA OVEN. | | | SECTION 106.1.1 2007 FBC. | | | 3) SEPARATE PLANS AND PERMIT REQUIRED FOR PIZZA OVEN, | | | WALK IN COOLER, WALK IN FREEZER. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 | | | [email protected] |
|