2011-06-14 15:59:33PLANS DENIED
 1) PAGE M1 A OF THE PLANS PROVIDE FIRE DAMPERS IN 12X14
 EXHAUST DUCT AND 12X12 EXHAUST DUCT .
 SECTION 607.5.1 2007 FBC (M)
 2) PROVIDE MANUFACTURE INSTALLATION INSTRUCTIONS FOR
 PIZZA OVEN.
 SECTION 106.1.1 2007 FBC.
 3) SEPARATE PLANS AND PERMIT REQUIRED FOR PIZZA OVEN,
 WALK IN COOLER, WALK IN FREEZER.