| 2011-05-27 16:11:52 | 1 NORTH CLEMATIS STREET, SUITE #110 |
| | PERMIT #11050710 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| | OF NFPA 241. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF |
| | THE FIRE MARSHAL. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHER LOCATIONS ON PLANS. |
| | EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC |
| | AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER |
| | COMPANY. TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT |
| | EXCEED 75 FEET. |
| | |
| | PROVIDE TACTILE SIGNAGE AT EXIT DOORS. |
| | |
| | IF ENTRY DOOR 102 IS EQUIPPED WITH A LATCH, PANIC |
| | HARDWARE IS NEEDED ON THIS EXISTING DOOR. |
| | |
| | THE OCCUPANT LOAD TO BE POSTED IN THE BUILDING INTERIOR |
| | SHOULD NOT INCLUDE THE EXTERIOR SEATING. |
| | |
| | INDICATE THE AMOUNT OF COAL THAT CAN BE STORED IN THE |
| | COAL STORAGE COMPARTMENT OF THE BRICK OVEN. NOTE: PER |
| | NFPA 96 SECTION 14.9.2.1. FUEL STORAGE SHALL NOT EXCEED |
| | A ONE-DAY SUPPLY WHERE STORAGE IS LOCATED IN THE SAME |
| | ROOM AS THE SOLID FUELED APPLIANCE, OR IN THE SAME |
| | ROOMS AS THE FUEL-LOADING OR CLEAN-OUT DOORS. |
| | |
| | PER NFPA 96 SECTION14.9.3.7.3 APPLIANCES WITH FIREBOXES |
| | OVER 5 FT3 THE WATER SOURCE SHALL BE A FIXED PIPE WATER |
| | SYSTEM WITH A HOSE OF ADEQUATE LENGTH TO REACH THE |
| | COMBUSTION AND COOKING CHAMBERS OF THE APPLIANCE. |
| | |
| | ALL OVEN ASH SHALL BE REMOVED FROM THE ASH COMPARTMENT |
| | AT LEAST ONCE PER DAY. THE ASH SHALL BE SPRAYED |
| | ADEQUATELY WITH WATER BEFORE REMOVAL TO EXTINGUISH ANY |
| | HOT ASH OR CINDERS AND TO CONTROL THE DUST WHEN THE ASH |
| | IS MOVED. |
| | |
| | PER NFPA 96 SECTION 14.9.3.8.1 A HEAVY METAL CONTAINER |
| | OR CART (MINIMUM 16 GAUGE) WITH A COVER SHALL BE |
| | PROVIDED FOR THE REMOVAL OF ASH. THE ASH REMOVAL |
| | CONTAINER OR CART SHALL NOT EXCEED A MAXIMUM OF 20 GAL |
| | CAPACITY, SHALL BE ASSIGNED FOR THIS ONE PURPOSE, SHALL |
| | BE ABLE TO BE HANDLED EASILY BY ANY EMPLOYEE ASSIGNED |
| | THE TASK, AND SHALL PASS EASILY THROUGH ANY PASSAGEWAY |
| | TO THE OUTSIDE OF THE BUILDING. THE CONTAINER OR CART |
| | SHALL ALWAYS BE COVERED WHEN IT IS BEING MOVED THROUGH |
| | THE PREMISES. |
| | |
| | FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SEALED |
| | CONSTRUCTION DOCUMENTS ARE REQUIRED FOR FIRE SPRINKLER |
| | AND FIRE ALARM INSTALLATION AND MODIFICATIONS. UNDER A |
| | SEPARATE PERMIT, SHOP DRAWINGS CONFORMING TO THE |
| | ENGINEER'S CONSTRUCTION DOCUMENTS WILL BE REQUIRED |
| | AFTER THE GENERAL BUILDING PERMIT HAS BEEN ISSUED. |
| | |
| | PROVIDE A DETAIL OF THE LARGE AMERITIC LIGHTING |
| | FIXTURES (P11). NOTE: THESE LIGHTING FIXTURES MAY |
| | OBSTRUCT THE AUTOMATIC SPRINKLERS. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |