| Notes |
| Date |
Text |
| 2011-05-31 12:55:59 | PROVIDE SPECIFICATIONS AND LISTING FOR P2 THRU P11 | | | CUSTOM BOTTLE LIGHTING FIXTURES SUPPLIED BY AMERITIC | | | LIGHTING. NEC 110.3 | | | PROVIDE STRUCTURAL SUPPORT DETAIL FOR P2 THRU P11 | | | CUSTOM FIXTURES SUPPLIED BY AMERITIC FOR LUMINARIES | | | RATED AT MORE THAN 50 POUNDS. NEC 410.36, 314.27 | | | GENERAL PURPOSE RECEPTACLES LOCATED AT BAR SINKS MUST | | | BE GFCI PROTECTED. NEC 210.8 (B) | | | A GFCI PROTECTED RECEPTACLE IS REQUIRED TO SERVICE THE | | | MECHANICAL EQUIPMENT ON THE ROOF. NEC 210.63 | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|