2011-08-12 09:29:03PROVIDE REVISED ELECTRICAL RISER PLAN. NEC 215.5
 RECEPTACLES IN BATHROOMS MUST BE GFCI PROTECTED. NEC
 210.8
 FIXTURES LOCATED IN THE TENT WASHING AREA MUST BE RATED
 FOR DAMP OR WET LOCATIONS. NEC 410.10
  
  