2011-06-01 14:48:38FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. SHEET A-6 ADA STALL - LAVATORY WOULD BE 1'-3" FROM
 SIDE WALL TO CENTER OF LAV IN 7'-1" STALL TO COMPLY
 WITH
 11-4.17 TOILET STALLS. FIGURE 30(E)
  
 2. SHEET P-200 SHOWS A TRENCH DRAIN ATTACHED TO THE
 GREASE LINE AND SHEET P-300 SHOWS IT ATTACHED TO THE
 OIL AND SAND INTERCEPTOR.
  
 3. SHEET P-200 + P-300 THE MOP SINK IS SHOWN CONNECTING
 TO THE W.C. WET VENT. CONNECTING THE STANDARD LAVS TO
 THE WC WOULD COMPLY WITH 909.1
 909.1 HORIZONTAL WET VENT PERMITTED. ANY COMBINATION OF
 FIXTURES WITHIN TWO BATHROOM GROUPS LOCATED ON THE SAME
 FLOOR LEVEL IS PERMITTED TO BE VENTED BY A HORIZONTAL
 WET VENT. THE WET VENT SHALL BE CONSIDERED THE VENT FOR
 THE FIXTURES AND SHALL EXTEND FROM THE CONNECTION OF
 THE DRY VENT ALONG THE DIRECTION OF THE FLOW IN THE
 DRAIN PIPE TO THE MOST DOWNSTREAM FIXTURE DRAIN
 CONNECTION TO THE HORIZONTAL BRANCH DRAIN. ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO
 THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT.
  
 4. SHEET P-400 GREASE TRAP DETAIL IS MISSING THE
 REQUIRED INLET DROP.
 1003.5.3 INLET AND OUTLET PIPING. INLET PIPING SHALL
 ENTER AT 2 1/2 INCHES (64 MM) ABOVE THE LIQUID LEVEL.
 INLET PIPING SHALL CONNECT TO A TEE, SWEEP OR BAFFLE,
 WHICH SHALL EXTEND TO 24 INCHES (610 MM) BELOW THE
 WATER LEVEL.
  
 5. 180 DEGREE WATER IS SHOWN TO DISH WASHERS.
 701.7 CONNECTIONS. DIRECT CONNECTION OF A STEAM
 EXHAUST, BLOWOFF OR DRIP PIPE SHALL NOT BE MADE WITH
 THE BUILDING DRAINAGE SYSTEM. WASTEWATER WHEN
 DISCHARGED INTO THE BUILDING DRAINAGE SYSTEM SHALL BE
 AT A TEMPERATURE NOT HIGHER THAN 140 DEGREE F (60?C).
 WHEN HIGHER TEMPERATURES EXIST, APPROVED COOLING
 METHODS SHALL BE PROVIDED.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  
  
  
  