| 2011-06-01 14:48:38 | FBC PLUMBING 2007 REVIEW #1 |
| | DENIED: |
| | |
| | 1. SHEET A-6 ADA STALL - LAVATORY WOULD BE 1'-3" FROM |
| | SIDE WALL TO CENTER OF LAV IN 7'-1" STALL TO COMPLY |
| | WITH |
| | 11-4.17 TOILET STALLS. FIGURE 30(E) |
| | |
| | 2. SHEET P-200 SHOWS A TRENCH DRAIN ATTACHED TO THE |
| | GREASE LINE AND SHEET P-300 SHOWS IT ATTACHED TO THE |
| | OIL AND SAND INTERCEPTOR. |
| | |
| | 3. SHEET P-200 + P-300 THE MOP SINK IS SHOWN CONNECTING |
| | TO THE W.C. WET VENT. CONNECTING THE STANDARD LAVS TO |
| | THE WC WOULD COMPLY WITH 909.1 |
| | 909.1 HORIZONTAL WET VENT PERMITTED. ANY COMBINATION OF |
| | FIXTURES WITHIN TWO BATHROOM GROUPS LOCATED ON THE SAME |
| | FLOOR LEVEL IS PERMITTED TO BE VENTED BY A HORIZONTAL |
| | WET VENT. THE WET VENT SHALL BE CONSIDERED THE VENT FOR |
| | THE FIXTURES AND SHALL EXTEND FROM THE CONNECTION OF |
| | THE DRY VENT ALONG THE DIRECTION OF THE FLOW IN THE |
| | DRAIN PIPE TO THE MOST DOWNSTREAM FIXTURE DRAIN |
| | CONNECTION TO THE HORIZONTAL BRANCH DRAIN. ONLY THE |
| | FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO |
| | THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL |
| | FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL |
| | WET VENT. |
| | |
| | 4. SHEET P-400 GREASE TRAP DETAIL IS MISSING THE |
| | REQUIRED INLET DROP. |
| | 1003.5.3 INLET AND OUTLET PIPING. INLET PIPING SHALL |
| | ENTER AT 2 1/2 INCHES (64 MM) ABOVE THE LIQUID LEVEL. |
| | INLET PIPING SHALL CONNECT TO A TEE, SWEEP OR BAFFLE, |
| | WHICH SHALL EXTEND TO 24 INCHES (610 MM) BELOW THE |
| | WATER LEVEL. |
| | |
| | 5. 180 DEGREE WATER IS SHOWN TO DISH WASHERS. |
| | 701.7 CONNECTIONS. DIRECT CONNECTION OF A STEAM |
| | EXHAUST, BLOWOFF OR DRIP PIPE SHALL NOT BE MADE WITH |
| | THE BUILDING DRAINAGE SYSTEM. WASTEWATER WHEN |
| | DISCHARGED INTO THE BUILDING DRAINAGE SYSTEM SHALL BE |
| | AT A TEMPERATURE NOT HIGHER THAN 140 DEGREE F (60?C). |
| | WHEN HIGHER TEMPERATURES EXIST, APPROVED COOLING |
| | METHODS SHALL BE PROVIDED. |
| | |
| | REVIEW BY |
| | LARRY WAGNER |
| | CHIEF PLUMBING INSPECTOR |
| | PHONE # 805-6692 |
| | EMAIL [email protected] |
| | FAX # 805-6676 |
| | |
| | |
| | |
| | |
| | |