2011-06-09 08:34:30****CORRECTIONS****
  
 1. PROVIDE THE ROOF STAND PRODUCT APPROVAL, FAC9N-3.
  
 2. SPECIFY THE FOLLOWING BOLT SIZES (DIAMETER, LENGTH,
 TYPE) FOR DETAIL CONDENSING UNIT MOUNTING DETAIL ON
 SHEET M 401, IF INFORMATION IS NOT INCLUDED IN THE ROOF
 STAND PRODUCT APPROVAL:
  
 STAND TO CONCRETE ROOF
 ANGLE TO STAND
  
 THIS REVIEW CAN BE PASSED WITH PROVISO (REVISION
 REQUIRED, WITH ADDITIONAL FEES) UPON REQUEST FROM THE
 ENGINEER.
  