| 2011-06-03 15:39:02 | 5657 45TH STREET |
| | PERMIT #11050669 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. |
| | NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND |
| | SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION |
| | 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE NFPA 1). |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF |
| | THE FIRE MARSHAL. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| | FIRE/SMOKE BARRIER?PROTECT ALL OPENINGS. CHARACTERS |
| | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| | FEET ON CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA |
| | FIRE PREVENTION CODE NFPA 101 |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHER IN NEW |
| | SHOWROOM/OFFICE SPACE AS TRAVEL DISTANCE APPEARS TO |
| | EXCEED 75 FEET TO EXTINGUISHERS LOCATED IN WAREHOUSE |
| | AREA. |
| | |
| | PROVIDE SOME INFORMATION WITH REGARDS TO THE RACK |
| | STORAGE SUCH AS ESTIMATED STORAGE HEIGHT, STORAGE TYPE |
| | (PILED, PALLET, ETC.), COMMODITY ETC. |
| | |
| | PROVIDE ADDITIONAL INFORMATION FOR THE PROPANE STORAGE |
| | BUILDING. INDICATE CONTAINER SIZES, QUANTITIES ETC. |
| | |
| | SHEET E-300: REMOVE WAREHOUSE EXIT SIGNS LEADING BACK |
| | INTO NEW OFFICE SPACE BECUASE DOOR #10 AND #12 REQUIRE |
| | A CARD OR KEY PAD FOR ENTRY. |
| | |
| | SHEET F-100 DOES NOT PROVIDE ANY SCOPE OF WORK FOR THE |
| | WAREHOUSE/STORAGE AREA. |
| | |
| | SHEET P-302: UNDERGROUND LP STORAGE TANK SHALL CONFORM |
| | TO THE REQUIREMENTS OF THE FLORIDA FIRE PREVENTION |
| | CODE, NFPA 54 AND NFPA 58. INDICATE THE SIZE OF THE LP |
| | STORAGE TANK AND ANY INTENDED SAFEGUARDS. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |