Plan Review Notes
Plan Review Notes For Permit 11050669
Permit Number 11050669
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-06-03 15:39:025657 45TH STREET
 PERMIT #11050669
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND
 SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION
 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE NFPA 1).
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF
 THE FIRE MARSHAL.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER?PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA
 FIRE PREVENTION CODE NFPA 101
  
 PROVIDE PORTABLE FIRE EXTINGUISHER IN NEW
 SHOWROOM/OFFICE SPACE AS TRAVEL DISTANCE APPEARS TO
 EXCEED 75 FEET TO EXTINGUISHERS LOCATED IN WAREHOUSE
 AREA.
  
 PROVIDE SOME INFORMATION WITH REGARDS TO THE RACK
 STORAGE SUCH AS ESTIMATED STORAGE HEIGHT, STORAGE TYPE
 (PILED, PALLET, ETC.), COMMODITY ETC.
  
 PROVIDE ADDITIONAL INFORMATION FOR THE PROPANE STORAGE
 BUILDING. INDICATE CONTAINER SIZES, QUANTITIES ETC.
  
 SHEET E-300: REMOVE WAREHOUSE EXIT SIGNS LEADING BACK
 INTO NEW OFFICE SPACE BECUASE DOOR #10 AND #12 REQUIRE
 A CARD OR KEY PAD FOR ENTRY.
  
 SHEET F-100 DOES NOT PROVIDE ANY SCOPE OF WORK FOR THE
 WAREHOUSE/STORAGE AREA.
  
 SHEET P-302: UNDERGROUND LP STORAGE TANK SHALL CONFORM
 TO THE REQUIREMENTS OF THE FLORIDA FIRE PREVENTION
 CODE, NFPA 54 AND NFPA 58. INDICATE THE SIZE OF THE LP
 STORAGE TANK AND ANY INTENDED SAFEGUARDS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  