2011-05-26 08:16:56 
 MINIMUM SERVICE SIZE TO A SINGLE FAMILY DWELLING UNIT
 IS 100 AMPS. NEC 230.79 (C)
 ELECTRIC REPAIR OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS WITH BATTERY
 BACK UP LOCATED INSIDE AND OUTSIDE ALL SLEEPING AREAS.
 HOMES WHICH FEATURE GAS APPLIANCES, AN ATTACHED GARAGE
 OR A FIRE PLACE REQUIRE A CARBON MONOXIDE DETECTOR
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC
 R313
 PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE
 GROUND. NEC 250.94
 ALL NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC
 406.11,
 AFCI PROTECTION REQUIRED FOR GENERAL PURPOSE CIRCUITS
 WHICH ADDED OR REPAIRED. NEC 210-12
 VERIFY THE NEW SERVICE EQUIPMENT WILL INTERRUPT THE
 AVAILABLE FAULT CURRENT. NEC 110.9
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  