| Plan Review Notes For Permit 11050655 |
| Permit Number |
11050655 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-05-26 08:13:12 | | | | MINIMUM SERVICE SIZE TO A SINGLE FAMILY DWELLING UNIT | | | IS 100 AMPS. NEC 230.79 (C) | | | ELECTRIC REPAIR OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS WITH BATTERY | | | BACK UP LOCATED INSIDE AND OUTSIDE ALL SLEEPING AREAS. | | | HOMES WHICH FEATURE GAS APPLIANCES, AN ATTACHED GARAGE | | | OR A FIRE PLACE REQUIRE A CARBON MONOXIDE DETECTOR | | | WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC | | | R313 | | | PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE | | | GROUND. NEC 250.94 | | | ALL NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC | | | 406.11, | | | AFCI PROTECTION REQUIRED FOR GENERAL PURPOSE CIRCUITS | | | WHICH ADDED OR REPAIRED. NEC 210-12 | | | VERIFY THE NEW SERVICE EQUIPMENT WILL INTERRUPT THE | | | AVAILABLE FAULT CURRENT. NEC 110.9 | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|