| Notes |
| Date |
Text |
| 2011-05-23 11:34:00 | PROVIDE AN ELECTRIC SERVICE RISER PLAN FOR NEW SERVICE. | | | SHOW GROUNDING, WIRE SIZE AND MAIN DISCONNECT. INDICATE | | | LOCATION OF PANEL BOARD. PROVIDE A PANEL SCHEDULE | | | SHOWING NEW AND EXISTING LOADS. NEC 215.5 | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT | | | ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE | | | HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE | | | A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET | | | OF EACH ROOM USED FOR SLEEPING. FBC R313 | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE | | | GROUND. NEC 250.94 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|