2012-07-09 14:19:16FBC 2007 PLUMBING REVIEW #5
 DENIED:
  
 FROM LAST REVIEW:
  
 2. THE SUMP PUMP SHOWN WILL BE REQUIRED TO CONNECT
 INDIRECTLY (TO A FLOOR DRAIN OR HUB DRAIN) TO THE
 **SANITARY** USING THE OIL SMART CONTROLS SHOWN ON
 P3-1.
 WITH THE USE OF THE OIL SMART CONTROLS, THE OIL
 INTERCEPTOR WOULD NOT BE REQUIRED.
 301.6 PROHIBITED LOCATIONS. PLUMBING SYSTEMS SHALL NOT
 BE LOCATED IN AN ELEVATOR SHAFT OR IN AN ELEVATOR
 EQUIPMENT ROOM.
 EXCEPTION: FLOOR DRAINS, SUMPS AND SUMP PUMPS SHALL BE
 PERMITTED AT THE BASE OF THE SHAFT PROVIDED THEY ARE
 ***INDIRECTLY*** CONNECTED TO THE PLUMBING SYSTEM.
 THE SUMP LINE WILL NOT BE CONNECTED TO THE STORM SYSTEM
 - CITY UTILITY CODE 90-203 (A)
  
 PLEASE CORRECT THE FOLLOWING:
  
 1. WHILE SHEET P3-2 FIXTURE TABLE LISTS P-2 AS A
 REGULAR WATER CLOSET P-3 AS A WALL HUNG LAV.
 A. SHEET P2-2 SHOWS REGULAR WATER CLOSETS AS P-3 AND
 WALL HUNG LAVS. AS P-2
 B. SHEET P3-3 SHOWS THE MEZZANINE A REGULAR WATER
 CLOSET (2 WC'S ARE MISSING) AS P-3 AND 2 WALL HUNG LAVS
 AS P-2
 C. SHEET P3-3 THE WATER PIPE ISO SHOWS 3 WC'S AS P-3 ,
 ALSO THE WALL HUNG LAVS APPEAR TO BE MISSING.
  