Plan Review Notes
Plan Review Notes For Permit 11050596
Permit Number 11050596
Review Stop B
Sequence Number 4
Notes
Date Text
2012-06-25 16:51:38BUILDING PLAN REVIEW
 PERMIT: 11050596
 ADD: 114 S OLIVE AVE
 CONT: LAKESIDE CONTRACTING CORP
 TEL: (954)553-8398
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 2007/09 FLORIDA EXISTING BUILDING CODE W/ SUPPLEMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 JUNE 25,/ 2012
 ACTION: DENIED
  
 NOTE: WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY
 MAKING TWO COMPLETE SETS OF PLANS. PLANS WERE SUBMITTED
 IN INCOMPLETE SETS MAKING A PLAN REVIEW OF 4 PARTIAL
 SETS VERY TIME CONSUMING AND WHAT STILL LOOKS OR
 APPEARS TO BE INCOMPLETE PLANS! A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1) COMPLIED.
  
 2) 4TH REQUEST, NOT FOUND ON EITHER THE COVER SHEET NOR
 LS-01. WHAT WAS THE LAST KNOWN USE FOR THIS BUILDING,
 IS THIS A CHANGE OF OCCUPANCY? THE PLANS DO NOT
 REFERENCE THE FLORIDA EXISTING BUILDING CODE AND TO
 WHICH TYPE OF COMPLIANCE METHOD THE PLANS WERE DESIGNED
 TOO? FL EXST BLDG CODE 101.5 (.1-.3).RESPONCE INDICATES
 THE LAST KNOWN USE A RESTARAUNT. THE PALM BEACH COUNTY
 IMPACT FEE OFFICE INDICATES THE LAST KNOWN USE TO BE A
 BUSINESS OFFICE NOT A RESTARAUNT, THIS TRIGGERS THE
 2007 EXISTING BUILDING CODE CHAPTER 9 SECTION 901.3AND
 THE PROVISIONS OF 902 THROUGH 912 OF THE EXISTING
 BUILDING CODE SHALL APPLY.
  
 3A) FOURTH REQUEST, PLEASE REFER TO THE 2007 FBC-B FOR
 BUILDING TYPE, NOTE THE 2007FBC-B 603.1.3 REQUIRES ALL
 ROOF CONSTRUCTION GIRDERS, JOIST, TRUSSES AND DECKING
 ARE TO BE FIRE RETARDANT TREATED WOOD. SHEET S-5
 INDICATES THE EXISTING 2X6 ROOF FRAMING, IS THE
 EXISTING STRUCTURE TRULY A BUILDING TYPE II-B? PLEASE
 NOTE THE NEW FRAMING MEMBERS LOCATED ON SHEET S-5 DO
 NOT INDICATE THE USE OF FIRE RETARDANT TREATED WOOD.
 SHEET INDICATES THE USE OF EXISTING 2X6 ROOF JOISST AND
 DECKING TO REMAIN. HOW WILL THIS ISSUE BE
 RESOLVED??????? PLANS INDICATE THIS IS A TYPE II-B
 CONSTRUCTION.
  
 3B) COMPLIED.
  
 4-7) COMPLIED.
  
 8) SEMI-COMPLIED, RE
  
 THE RESPONCE LETTER INDICATES THE ELEVATOR TO BE A
 SCHINDLER 3300 MRL ELECTRIC TRACTION ELEVATOR, PLEASE
 PROVIDE DOCUMENTATION THIS ELEVATOR MEETS THE
 REQUIREMENTS OF 3001.2 REFERENCED STANDARDS AND
 ACCESSIBILITY REQUIREMENTS. FORMER COMMENT .PLEASE
 INDICATE WHERE THE ELEVATOR HYDROLIC PUMP (MACHINE
 ROOM) WILL BE LOCATED. . PLEASE PROVIDE INFORMATION AS
 TO SHEET A2-01 & LS-01 WHAT IS THE ROOM # 119 USED FOR
 IS THIS THE ELEVATOR MACHINE ROOM? IF SO IT NEEDS TO BE
 RATED AS DOES THE DOOR.
  
  
 THIS REVIEW WILL CONTINUE TUESDAY 6/26/2012
  
  
 9) 4TH REQUEST. SHEET A2-01 INDICATES NEW RAISED
 PLATFORM FLOORING PLEASE PROVIDE SQUARE FOOTAGE OF
 RAISED PLATFORM FLOORING, PLEASE REVIEW SECTION 2007/09
 FBC-B 410.4 FIRE RETARDANT TREATED WOOD REQUIREMENT.
 THE STRUCTURAL S-4 DATED 01-04-12 STILL INDICATES WOOD
 FRAMING THE NEW S-2 05/04/12 INDICATES STEEL JOIST,
 STEEL PAN AND CONCRETE
 FLOOR FINISH PLEASE REVIEW ALL SHEETS FOR CODE
 COMPLIANCE.
  
 10) 4TH REQUEST. STRUCTURAL PLANS SUBMITTED S-2 DATED
 05-04-12 STILL HAS A DISCREPANCY AS TO WHAT APPEARS TO
 BE A DOORWAY THAT WOULD LED INTO THE LADIES RESTROOM
 FROM THE STAIR.DISCREPANCY IN PLANS. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 11) 4TH REQUEST ROOF HATCH PLEASE BE AWARE OF
 ADDITIONAL INFORMATION REQUIRED, SHEET A2.04 INDICATES
 THE USE OF A NEW ROOF HATCH ANS DETAIL TO BE LOCATED ON
 SHEET DETAIL # 11 A7.02. MISSING SHEET A7.02. PLEASE
 SEE FBC-B 1013.5. & 2007/09 MECH CODE 304.10 FOR GUARD
 REQUIREMENTS WHEN UNITS ARE WITHIN 10'-0" OF THE ROOF
 EDGE.
  
 ***** NOTED RESPONCE TO KEEP EQUIPMENT 10'-0" AWAY FROM
 EDGE OF ROOF.*****
  
 11A) GUARDS SHALL BE PROVIDED WHERE APPLIANCES,
 EQUIPMENT, FANS, ROOF HATCH OPENINGS OR OTHER
 COMPONENTS THAT REQUIRE SERVICE ARE LOCATED WITHIN 10
 FEET (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING
 SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN
 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE
 BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT
 THE PASSAGE OF A 21-INCH-DIAMETER (533 MM) SPHERE. THE
 GUARD SHALL EXTEND NOT LESS THAN 30 INCHES (762 MM)
 BEYOND EACH END OF SUCH APPLIANCE, EQUIPMENT, FAN OR
 COMPONENT.
  
 11B) 1013.6 ROOF ACCESS. GUARDS SHALL BE PROVIDED WHERE
 THE ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET (3048
 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE
 AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN 30
 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW.
 THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT THE
 PASSAGE OF A 21-INCH-DIAMETER (533 MM) SPHERE.
  
  
 12) COMPLIED.
  
 13) 4TH REQUEST. FL BLD CODE 1609.6.2.2 COMPONENTS &
 CLADDING, PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT
 INSPECTOR OF PRODUCT TESTING REPORTS, MISSING REPORTS
 ARE AS FOLLOWS:
 13A) WINDOWS
 13B) EXTERIOR DOORS
 13C) ROOF HATCH
 13D) A/C PRE-MANUFACTURED STANDS
  
 14) 4TH REQUEST. 106.3.3 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 15) COMPLIED.
  
 16)4TH REQUEST, SHEET A-2.01 THE PLANS DO NOT PROVIDE
 ELEVATION CHANGE FROM THE CONCRETE DECK TO FINISHED
 MAIN SEATING AREA NOT THE VIP PLATFORM. FBC-B 1003.5.2.
 NOR IS THERE A CUT SECTION THROUGH STAIRS FOR ACCESS TO
 PLATFROM AREAS. 2007 FBC 1009.3. RISE & RUN.
  
 17) 4TH REQUEST. RESPONCE COMMENTS INDICATE STAIR
 DETAILS FOR STAIR # 2 ARE TO BE FOUND ON A4-03, A4-04
 AND DETAIL #4 ON SHEET A4-06.
 THE NUMBERED SHEETS STATED IN RESPONCE WERE NOT FOUND
 IN THE FOURTH SUBMITAL, NOR ON SHEETS DATED 2/16/12 NOR
 1/06/12/
 SHEET A-5.02 STAIRWELL # 2. NO STRUCTURAL PLANS WERE
 SUBMITTED THE TYPE OF MATEIAL FOR STAIR CONSTRUCTION IS
 NOT PROVIDED 2007/09 FBC-B 1009.5 NOR IS THE RISE NOR
 RUN OF THE STAIRSFBC-B 1009.3.
  
 18) 4TH REVIEW NO NEW LS02 SHEETS SUBMITTED . SHEET
 LS-02 MEZZANINE RESTROOMS PLEASE SEE 11-4,11-4.1.3(11)
 IF TOILET ROOMS ARE PROVIDED, THEN EACH PUBLIC & COMMON
 USE TOILET ROOM SHALL COMPLY WITH 11-4.22.
 PLEASE REVIEW 11-4.22(1) DOORS SHALL NOT SWING INTO THE
 CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE SEE 202 &
 205 RESTROOM STALL DOOR SWINGS INTO THE REQUIRED CLEAR
 FLOOR SPACE FOR THE LAVATORY.
  
 19)4TH REVIEW 2007 EXISTING BUILDING CODE LEVEL II
 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 LS-01 THE VIP PLATFORM #108 & DANCE FLOOR # 107 WILL
 NEED TO COMPLY WITH VERTICAL ACCESSIBILITY REQUIREMENTS
 11-4.1.3(5).
  
 20) COMPLIED.
  
 21)4TH REVIEW, THIS COMMENT MAY OR MAY NOT BE RELEVENT.
 COMMENTS RESPONCE SHEET INDICATES THE USE OF A
 SCHINDLERE 3300 MRL ELEVATOR, TO DATE NO PRODUCT SPECS
 HAVE BEEN SUBMITTED FOR REVIEW.
 SHEET A4-04 & S-7 DETAIL #2 THE ELEVATOR SHAFT DETAIL
 IS MISSING THE SUMP PUMP DETAIL 09/A6.121 DETAIL NOT
 PROVIDED.
  
 22) NOT REQUIRED.
 -------------------------------------------------------
 ----------
  
 23) 4TH REQUEST. THERE IS A NEW 8X11 INTRODUCTORY
 OVERVIEW STATEMENT SHEET, INCLUDED IN THE PERMIT
 PACKAGE, AUTHOR UNKNOWN BUT THE COMMENT INDICATING THAT
 ALL INTERIOR FINISHES AND FINISH MATERIALS WILL BE
 SELECTED BY OWNER AND UNDER A SEPERATE CONTRACT SAID
 MATERIALS INCLUDE ALL FLOOR FINISHES, CEILING MATERIALS
 & FINISHES ALL WINDOW AND DOOR FINISHES, AND WALL
 SURFACE FINISHES.
  
 WITH THE ABOVE STATEMENT THE PERMIT CAN BE ISSUED AS A
 PROVISO, BUT A SECONDARY PERMIT WILL NEED TO BE APPLIED
 FOR BEFORE A C.O. WILL BE ISSUED.
 THE ARCHITECT OF RECORD SHOULD HAVE A STATEMENT ON THE
 PLANS INDICATING THAT FINISHES TO BE UNDER A SEPERATE
 PERMIT. 106.3.5.1.1. COMMERCIAL PLAN REVIEW CRITERIA
 WOULD REQUIRE THIS INFORMATION BEFORE A PERMIT COULD BE
 ISSUED, THAT WOULD BE THE REASON IT WOULD BE EXEMPTED
 FROM THIS PERMIT.
  
 24) THE NEW A SHEETS ARE SIGNED AND SEALED BUT NOT
 DATED.
 61G1-16.004 FL. ADMIN. CODE. PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 X= MISSING INFORMATION
 X - STATE THE FIRM NAME, ADDRESS AND TELEPHONE NUMBER
 X - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 X - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEALED
 INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING THE
 PLANS
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  