| 2012-06-25 16:51:38 | BUILDING PLAN REVIEW |
| | PERMIT: 11050596 |
| | ADD: 114 S OLIVE AVE |
| | CONT: LAKESIDE CONTRACTING CORP |
| | TEL: (954)553-8398 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | 2007/09 FLORIDA EXISTING BUILDING CODE W/ SUPPLEMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 4TH REVIEW |
| | JUNE 25,/ 2012 |
| | ACTION: DENIED |
| | |
| | NOTE: WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY |
| | MAKING TWO COMPLETE SETS OF PLANS. PLANS WERE SUBMITTED |
| | IN INCOMPLETE SETS MAKING A PLAN REVIEW OF 4 PARTIAL |
| | SETS VERY TIME CONSUMING AND WHAT STILL LOOKS OR |
| | APPEARS TO BE INCOMPLETE PLANS! A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 1) COMPLIED. |
| | |
| | 2) 4TH REQUEST, NOT FOUND ON EITHER THE COVER SHEET NOR |
| | LS-01. WHAT WAS THE LAST KNOWN USE FOR THIS BUILDING, |
| | IS THIS A CHANGE OF OCCUPANCY? THE PLANS DO NOT |
| | REFERENCE THE FLORIDA EXISTING BUILDING CODE AND TO |
| | WHICH TYPE OF COMPLIANCE METHOD THE PLANS WERE DESIGNED |
| | TOO? FL EXST BLDG CODE 101.5 (.1-.3).RESPONCE INDICATES |
| | THE LAST KNOWN USE A RESTARAUNT. THE PALM BEACH COUNTY |
| | IMPACT FEE OFFICE INDICATES THE LAST KNOWN USE TO BE A |
| | BUSINESS OFFICE NOT A RESTARAUNT, THIS TRIGGERS THE |
| | 2007 EXISTING BUILDING CODE CHAPTER 9 SECTION 901.3AND |
| | THE PROVISIONS OF 902 THROUGH 912 OF THE EXISTING |
| | BUILDING CODE SHALL APPLY. |
| | |
| | 3A) FOURTH REQUEST, PLEASE REFER TO THE 2007 FBC-B FOR |
| | BUILDING TYPE, NOTE THE 2007FBC-B 603.1.3 REQUIRES ALL |
| | ROOF CONSTRUCTION GIRDERS, JOIST, TRUSSES AND DECKING |
| | ARE TO BE FIRE RETARDANT TREATED WOOD. SHEET S-5 |
| | INDICATES THE EXISTING 2X6 ROOF FRAMING, IS THE |
| | EXISTING STRUCTURE TRULY A BUILDING TYPE II-B? PLEASE |
| | NOTE THE NEW FRAMING MEMBERS LOCATED ON SHEET S-5 DO |
| | NOT INDICATE THE USE OF FIRE RETARDANT TREATED WOOD. |
| | SHEET INDICATES THE USE OF EXISTING 2X6 ROOF JOISST AND |
| | DECKING TO REMAIN. HOW WILL THIS ISSUE BE |
| | RESOLVED??????? PLANS INDICATE THIS IS A TYPE II-B |
| | CONSTRUCTION. |
| | |
| | 3B) COMPLIED. |
| | |
| | 4-7) COMPLIED. |
| | |
| | 8) SEMI-COMPLIED, RE |
| | |
| | THE RESPONCE LETTER INDICATES THE ELEVATOR TO BE A |
| | SCHINDLER 3300 MRL ELECTRIC TRACTION ELEVATOR, PLEASE |
| | PROVIDE DOCUMENTATION THIS ELEVATOR MEETS THE |
| | REQUIREMENTS OF 3001.2 REFERENCED STANDARDS AND |
| | ACCESSIBILITY REQUIREMENTS. FORMER COMMENT .PLEASE |
| | INDICATE WHERE THE ELEVATOR HYDROLIC PUMP (MACHINE |
| | ROOM) WILL BE LOCATED. . PLEASE PROVIDE INFORMATION AS |
| | TO SHEET A2-01 & LS-01 WHAT IS THE ROOM # 119 USED FOR |
| | IS THIS THE ELEVATOR MACHINE ROOM? IF SO IT NEEDS TO BE |
| | RATED AS DOES THE DOOR. |
| | |
| | |
| | THIS REVIEW WILL CONTINUE TUESDAY 6/26/2012 |
| | |
| | |
| | 9) 4TH REQUEST. SHEET A2-01 INDICATES NEW RAISED |
| | PLATFORM FLOORING PLEASE PROVIDE SQUARE FOOTAGE OF |
| | RAISED PLATFORM FLOORING, PLEASE REVIEW SECTION 2007/09 |
| | FBC-B 410.4 FIRE RETARDANT TREATED WOOD REQUIREMENT. |
| | THE STRUCTURAL S-4 DATED 01-04-12 STILL INDICATES WOOD |
| | FRAMING THE NEW S-2 05/04/12 INDICATES STEEL JOIST, |
| | STEEL PAN AND CONCRETE |
| | FLOOR FINISH PLEASE REVIEW ALL SHEETS FOR CODE |
| | COMPLIANCE. |
| | |
| | 10) 4TH REQUEST. STRUCTURAL PLANS SUBMITTED S-2 DATED |
| | 05-04-12 STILL HAS A DISCREPANCY AS TO WHAT APPEARS TO |
| | BE A DOORWAY THAT WOULD LED INTO THE LADIES RESTROOM |
| | FROM THE STAIR.DISCREPANCY IN PLANS. 106.1.2 ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 11) 4TH REQUEST ROOF HATCH PLEASE BE AWARE OF |
| | ADDITIONAL INFORMATION REQUIRED, SHEET A2.04 INDICATES |
| | THE USE OF A NEW ROOF HATCH ANS DETAIL TO BE LOCATED ON |
| | SHEET DETAIL # 11 A7.02. MISSING SHEET A7.02. PLEASE |
| | SEE FBC-B 1013.5. & 2007/09 MECH CODE 304.10 FOR GUARD |
| | REQUIREMENTS WHEN UNITS ARE WITHIN 10'-0" OF THE ROOF |
| | EDGE. |
| | |
| | ***** NOTED RESPONCE TO KEEP EQUIPMENT 10'-0" AWAY FROM |
| | EDGE OF ROOF.***** |
| | |
| | 11A) GUARDS SHALL BE PROVIDED WHERE APPLIANCES, |
| | EQUIPMENT, FANS, ROOF HATCH OPENINGS OR OTHER |
| | COMPONENTS THAT REQUIRE SERVICE ARE LOCATED WITHIN 10 |
| | FEET (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING |
| | SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN |
| | 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE |
| | BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT |
| | THE PASSAGE OF A 21-INCH-DIAMETER (533 MM) SPHERE. THE |
| | GUARD SHALL EXTEND NOT LESS THAN 30 INCHES (762 MM) |
| | BEYOND EACH END OF SUCH APPLIANCE, EQUIPMENT, FAN OR |
| | COMPONENT. |
| | |
| | 11B) 1013.6 ROOF ACCESS. GUARDS SHALL BE PROVIDED WHERE |
| | THE ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET (3048 |
| | MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE |
| | AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 |
| | INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. |
| | THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT THE |
| | PASSAGE OF A 21-INCH-DIAMETER (533 MM) SPHERE. |
| | |
| | |
| | 12) COMPLIED. |
| | |
| | 13) 4TH REQUEST. FL BLD CODE 1609.6.2.2 COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT |
| | INSPECTOR OF PRODUCT TESTING REPORTS, MISSING REPORTS |
| | ARE AS FOLLOWS: |
| | 13A) WINDOWS |
| | 13B) EXTERIOR DOORS |
| | 13C) ROOF HATCH |
| | 13D) A/C PRE-MANUFACTURED STANDS |
| | |
| | 14) 4TH REQUEST. 106.3.3 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9B-72 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 15) COMPLIED. |
| | |
| | 16)4TH REQUEST, SHEET A-2.01 THE PLANS DO NOT PROVIDE |
| | ELEVATION CHANGE FROM THE CONCRETE DECK TO FINISHED |
| | MAIN SEATING AREA NOT THE VIP PLATFORM. FBC-B 1003.5.2. |
| | NOR IS THERE A CUT SECTION THROUGH STAIRS FOR ACCESS TO |
| | PLATFROM AREAS. 2007 FBC 1009.3. RISE & RUN. |
| | |
| | 17) 4TH REQUEST. RESPONCE COMMENTS INDICATE STAIR |
| | DETAILS FOR STAIR # 2 ARE TO BE FOUND ON A4-03, A4-04 |
| | AND DETAIL #4 ON SHEET A4-06. |
| | THE NUMBERED SHEETS STATED IN RESPONCE WERE NOT FOUND |
| | IN THE FOURTH SUBMITAL, NOR ON SHEETS DATED 2/16/12 NOR |
| | 1/06/12/ |
| | SHEET A-5.02 STAIRWELL # 2. NO STRUCTURAL PLANS WERE |
| | SUBMITTED THE TYPE OF MATEIAL FOR STAIR CONSTRUCTION IS |
| | NOT PROVIDED 2007/09 FBC-B 1009.5 NOR IS THE RISE NOR |
| | RUN OF THE STAIRSFBC-B 1009.3. |
| | |
| | 18) 4TH REVIEW NO NEW LS02 SHEETS SUBMITTED . SHEET |
| | LS-02 MEZZANINE RESTROOMS PLEASE SEE 11-4,11-4.1.3(11) |
| | IF TOILET ROOMS ARE PROVIDED, THEN EACH PUBLIC & COMMON |
| | USE TOILET ROOM SHALL COMPLY WITH 11-4.22. |
| | PLEASE REVIEW 11-4.22(1) DOORS SHALL NOT SWING INTO THE |
| | CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE SEE 202 & |
| | 205 RESTROOM STALL DOOR SWINGS INTO THE REQUIRED CLEAR |
| | FLOOR SPACE FOR THE LAVATORY. |
| | |
| | 19)4TH REVIEW 2007 EXISTING BUILDING CODE LEVEL II |
| | 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | LS-01 THE VIP PLATFORM #108 & DANCE FLOOR # 107 WILL |
| | NEED TO COMPLY WITH VERTICAL ACCESSIBILITY REQUIREMENTS |
| | 11-4.1.3(5). |
| | |
| | 20) COMPLIED. |
| | |
| | 21)4TH REVIEW, THIS COMMENT MAY OR MAY NOT BE RELEVENT. |
| | COMMENTS RESPONCE SHEET INDICATES THE USE OF A |
| | SCHINDLERE 3300 MRL ELEVATOR, TO DATE NO PRODUCT SPECS |
| | HAVE BEEN SUBMITTED FOR REVIEW. |
| | SHEET A4-04 & S-7 DETAIL #2 THE ELEVATOR SHAFT DETAIL |
| | IS MISSING THE SUMP PUMP DETAIL 09/A6.121 DETAIL NOT |
| | PROVIDED. |
| | |
| | 22) NOT REQUIRED. |
| | ------------------------------------------------------- |
| | ---------- |
| | |
| | 23) 4TH REQUEST. THERE IS A NEW 8X11 INTRODUCTORY |
| | OVERVIEW STATEMENT SHEET, INCLUDED IN THE PERMIT |
| | PACKAGE, AUTHOR UNKNOWN BUT THE COMMENT INDICATING THAT |
| | ALL INTERIOR FINISHES AND FINISH MATERIALS WILL BE |
| | SELECTED BY OWNER AND UNDER A SEPERATE CONTRACT SAID |
| | MATERIALS INCLUDE ALL FLOOR FINISHES, CEILING MATERIALS |
| | & FINISHES ALL WINDOW AND DOOR FINISHES, AND WALL |
| | SURFACE FINISHES. |
| | |
| | WITH THE ABOVE STATEMENT THE PERMIT CAN BE ISSUED AS A |
| | PROVISO, BUT A SECONDARY PERMIT WILL NEED TO BE APPLIED |
| | FOR BEFORE A C.O. WILL BE ISSUED. |
| | THE ARCHITECT OF RECORD SHOULD HAVE A STATEMENT ON THE |
| | PLANS INDICATING THAT FINISHES TO BE UNDER A SEPERATE |
| | PERMIT. 106.3.5.1.1. COMMERCIAL PLAN REVIEW CRITERIA |
| | WOULD REQUIRE THIS INFORMATION BEFORE A PERMIT COULD BE |
| | ISSUED, THAT WOULD BE THE REASON IT WOULD BE EXEMPTED |
| | FROM THIS PERMIT. |
| | |
| | 24) THE NEW A SHEETS ARE SIGNED AND SEALED BUT NOT |
| | DATED. |
| | 61G1-16.004 FL. ADMIN. CODE. PLANS PREPARED BY A |
| | REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH |
| | MUST: |
| | X= MISSING INFORMATION |
| | X - STATE THE FIRM NAME, ADDRESS AND TELEPHONE NUMBER |
| | X - STATE THE FIRM LICENSE NUMBER |
| | - STATE PROJECT NAME OR IDENTIFICATION |
| | - STATE DATE PREPARED |
| | X - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEALED |
| | INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING THE |
| | PLANS |
| | |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER C.B.O. |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: (561)805-6715 |
| | FAX:(561)805-6731 |
| | E-MAIL: [email protected] |
| | |