| Notes |
| Date |
Text |
| 2012-03-01 13:26:10 | FBC PLUMBING 2007 REVIEW #2 | | | DENIED: | | | | | | 1. THE LATEST SUBMITTED PLANS DATED 2/16/12 DO NOT | | | INCLUDE PLUMBING DRAWINGS. | | | | | | OLD P3-3 ISOMETRIC DRAWINGS DO NOT REFLECT THE NEW | | | P2-1- P2-2 PLUMBING DRAWINGS. NEW P3-3 ISOMETRICS WERE | | | NOT INCLUDED WITH RE-SUBMITTAL DRAWINGS. | | | | | | 2. THE SUMP PUMP SHOWN WILL BE REQUIRED TO CONNECT | | | INDIRECTLY (TO A FLOOR DRAIN OR HUB DRAIN) TO THE | | | **SANITARY** USING THE OIL SMART CONTROLS SHOWN ON | | | P3-1. | | | WITH THE USE OF THE OIL SMART CONTROLS, THE OIL | | | INTERCEPTOR WOULD NOT BE REQUIRED. | | | 301.6 PROHIBITED LOCATIONS. PLUMBING SYSTEMS SHALL NOT | | | BE LOCATED IN AN ELEVATOR SHAFT OR IN AN ELEVATOR | | | EQUIPMENT ROOM. | | | EXCEPTION: FLOOR DRAINS, SUMPS AND SUMP PUMPS SHALL BE | | | PERMITTED AT THE BASE OF THE SHAFT PROVIDED THEY ARE | | | INDIRECTLY CONNECTED TO THE PLUMBING SYSTEM. | | | THE SUMP LINE WILL NOT BE CONNECTED TO THE STORM SYSTEM | | | - CITY UTILITY CODE 90-203 (A) | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | | | | | | | | | | |
|