Plan Review Notes
Plan Review Notes For Permit 11050596
Permit Number 11050596
Review Stop P
Sequence Number 3
Notes
Date Text
2012-03-01 13:26:10FBC PLUMBING 2007 REVIEW #2
 DENIED:
  
 1. THE LATEST SUBMITTED PLANS DATED 2/16/12 DO NOT
 INCLUDE PLUMBING DRAWINGS.
  
 OLD P3-3 ISOMETRIC DRAWINGS DO NOT REFLECT THE NEW
 P2-1- P2-2 PLUMBING DRAWINGS. NEW P3-3 ISOMETRICS WERE
 NOT INCLUDED WITH RE-SUBMITTAL DRAWINGS.
  
 2. THE SUMP PUMP SHOWN WILL BE REQUIRED TO CONNECT
 INDIRECTLY (TO A FLOOR DRAIN OR HUB DRAIN) TO THE
 **SANITARY** USING THE OIL SMART CONTROLS SHOWN ON
 P3-1.
 WITH THE USE OF THE OIL SMART CONTROLS, THE OIL
 INTERCEPTOR WOULD NOT BE REQUIRED.
 301.6 PROHIBITED LOCATIONS. PLUMBING SYSTEMS SHALL NOT
 BE LOCATED IN AN ELEVATOR SHAFT OR IN AN ELEVATOR
 EQUIPMENT ROOM.
 EXCEPTION: FLOOR DRAINS, SUMPS AND SUMP PUMPS SHALL BE
 PERMITTED AT THE BASE OF THE SHAFT PROVIDED THEY ARE
 INDIRECTLY CONNECTED TO THE PLUMBING SYSTEM.
 THE SUMP LINE WILL NOT BE CONNECTED TO THE STORM SYSTEM
 - CITY UTILITY CODE 90-203 (A)
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  
  
  