2012-04-13 10:02:36BUILDING PLAN REVIEW
 PERMIT: 11050596
 ADD: 114 S OLIVE AVE
 CONT: LAKESIDE CONTRACTING CORP
 TEL: (954)553-8398
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 2007/09 FLORIDA EXISTING BUILDING CODE W/ SUPPLEMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 APRIL 13,/ 2012
 ACTION: DENIED
  
 NOTE: THERE ARE NO STRUCTURAL SHEETS IN EITHER SET OF
 PLANS!!!!! NO S SHEETS!!!!
  
 1) COMPLIED.
  
 2) 3RD REQUEST, NOT FOUND ON EITHER THECOVER SHEET NOR
 LS-01. WHAT WAS THE LAST KNOWN USE FOR THIS BUILDING,
 IS THIS A CHANGE OF OCCUPANCY? THE PLANS DO NOT
 REFERENCE THE FLORIDA EXISTING BUILDING CODE AND TO
 WHICH TYPE OF COMPLIANCE METHOD THE PLANS WERE DESIGNED
 TOO? FL EXST BLDG CODE 101.5 (.1-.3).
  
 3A) THIRD REQUEST, NO STRUCTURAL SHEETS WERE SUBMITTED
 FOR THIS REVIEW. PLEASE REFER TO THE 2007 FBC-B FOR
 BUILDING TYPE, NOTE THE 2007FBC-B 603.1.3 REQUIRES ALL
 ROOF CONSTRUCTION GIRDERS, JOIST, TRUSSES AND DECKING
 ARE TO BE FIRE RETARDANT TREATED WOOD. SHEET S-5
 INDICATES THE EXISTING 2X6 ROOF FRAMING, IS THE
 EXISTING STRUCTURE TRULY A BUILDING TYPE II-B? PLEASE
 NOTE THE NEW FRAMING MEMBERS LOCATED ON SHEET S-5 DO
 NOT INDICATE THE USE OF FIRE RETARDANT TREATED WOOD.
 SHEET INDICATES THE USE OF EXISTING 2X6 ROOF JOISST AND
 DECKING TO REMAIN. HOW WILL THIS ISSUE BE
 RESOLVED??????? THIS IS A TYPE II-B CONSTRUCTION.
  
 3B) COMPLIED.
  
 4-7) COMPLIED.
  
 8) SEMI-COMPLIED, PLEASE INDICATE WHERE THE ELEVATOR
 HYDROLIC PUMP (MACHINE ROOM) WILL BE LOCATED. . PLEASE
 PROVIDE INFORMATION AS TO SHEET A2-01 & LS-01 WHAT IS
 THE ROOM # 119 USED FOR IS THIS THE ELEVATOR MACHINE
 ROOM? IF SO IT NEEDS TO BE RATED AS DOES THE DOOR.
  
 9) 3RD REQUEST. SHEET A2-01 INDICATES NEW RAISED
 PLATFORM FLOORING PLEASE PROVIDE SQUARE FOOTAGE OF
 RAISED PLATFORM FLOORING, PLEASE REVIEW SECTION 2007/09
 FBC-B 410.4 FIRE RETARDANT TREATED WOOD REQUIREMENT.
 SECTION 410.4 ONLY ALLOWS 1/3RD OFTHE FLOOR AREA WITHIN
 A ROOM TO BE ELEVATED. SHEET LS-01 THE ROOM SIZE
 TABULATION IS NOT CLOSE IN AREAS MISSING ONE MENS
 RESTROOM AND IT APPEARS THAT FOR ONE OF THE LADIES
 RESTROOM THE UNISEX RESTROOM WAS PUT IN TWICE AS A
 LADIES RESTROOM.
  
 10) 3RD REQUEST. NO STRUCTURAL PLANS WERE BROUGHT IN AT
 THIS TIME TO VERIFY.IT APPEARS THERE MAY BE A
 DISCREPANCY BETWEEN A2-01 & S-2, ON SHEET S-2 IT
 APPEARS THERE IS A DOORWAY THAT LEADS FROM THE RAISED
 DECK IN TO THE STAIRWELL WITH NO LANDING OR STAIRS.
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 11) ROOF HATCH PLEASE BE AWARE OF ADDITIONAL
 INFORMATION REQUIRED, SHEET A2.04 INDICATES THE USE OF
 A NEW ROOF HATCH ANS DEETAIL TO BE LOCATED ON SHEET
 DETAIL # 11 A7.02. MISSING SHEET A7.02. PLEASE SEE
 FBC-B 1013.5. & 2007/09 MECH CODE 304.10 FOR GUARD
 REQUIREMENTS WHEN UNITS ARE WITHIN 10'-0" OF THE ROOF
 EDGE.
  
 11A) GUARDS SHALL BE PROVIDED WHERE APPLIANCES,
 EQUIPMENT, FANS, ROOF HATCH OPENINGS OR OTHER
 COMPONENTS THAT REQUIRE SERVICE ARE LOCATED WITHIN 10
 FEET (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING
 SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN
 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE
 BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT
 THE PASSAGE OF A 21-INCH-DIAMETER (533 MM) SPHERE. THE
 GUARD SHALL EXTEND NOT LESS THAN 30 INCHES (762 MM)
 BEYOND EACH END OF SUCH APPLIANCE, EQUIPMENT, FAN OR
 COMPONENT.
  
 11B) 1013.6 ROOF ACCESS. GUARDS SHALL BE PROVIDED WHERE
 THE ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET (3048
 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE
 AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN 30
 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW.
 THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT THE
 PASSAGE OF A 21-INCH-DIAMETER (533 MM) SPHERE.
  
  
 12) COMPLIED.
  
 13) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 13A) WINDOWS
 13B) EXTERIOR DOORS
 13C) ROOF HATCH
 13D) A/C PRE-MANUFACTURED STANDS
  
 14) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 15) SHEET A5-01 STAIR # 1 INDICATES DETAIL 01 ON A-5.03
 INDICATES THE USE OF 2X WOOD STRINGERS. 2007/09 FBC-B
 1009.5 STAIRWAY CONSTRUCTION. ALL STAIRWAYS SHALL BE
 BUILT OF MATERIALS CONSISTENT WITH THE TYPES PERMITTED
 FOR THE TYPE OF CONSTRUCTION OF THE BUILDING,
  
 15B) SHEET A5-03 DETAIL 01 DOES NOT PROVIDE THE RISER
 DIMENSION FOR STAIRS. 2007/09 FBC-B 1009.3.
  
 16) SHEET A-2.01 THE PLANS DO NOT PROVIDE ELEVATION
 CHANGE FROM THE CONCRETE DECK TO FINISHED MAIN SEATING
 AREA NOT THE VIP PLATFORM. FBC-B 1003.5.2.
  
 17) SHEET A-5.02 STAIRWELL # 2. NO STRUCTURAL PLANS
 WERE SUBMITTED THE TYPE OF MATEIAL FOR STAIR
 CONSTRUCTION IS NOT PROVIDED 2007/09 FBC-B 1009.5 NOR
 IS THE RISE NOR RUN OF THE STAIRSFBC-B 1009.3.
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 NEW COMMENTS
  
 17) A4-03 & A4-04 :
  
 17A) SEE DETAIL # 4 ON A-34 MISSING SHEET
  
 17B) THE OLD PLANS INDICATE A ROOF / CEILING ASSEMBLY
 WITH A WIDE BLACK LINE. THE NEW PLANS INDICATE A
 SEPERATE WOOD ROOF JOIST SYSTEM AND A SEPERATE WOOD
 CEIING JOIST SYSTEM HOW ARE YOU GOING TO COMPLY AS A
 TYPE II-B BUILDING WITH NO COMBUSTIBLE FRAMING MEMBERS?
 2007/09 FBC-B 603.1 & TABLE 601.
  
 17C) A4-03 ALSO INDICATES A DETAIL # 11 SHEET A8.04 NOT
 IN PLANS?
  
 18) SHEET LS-02 MEZZANINE RESTROOMS PLEASE SEE
 11-411-4.1.3(11) IF TOILET ROOMS ARE PROVIDED, THEN
 EACH PUBLIC & COMMON USE TOILET ROOM SHALL COMPLY WITH
 11-4.22.
 PLEASE REVIEW 11-4.22(1) DOORS SHALL NOT SWING INTO THE
 CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE.
  
 19) 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 LS-01 THE VIP PLATFORM #108 & DANCE FLOOR # 107 WILL
 NEED TO COMPLY WITH VERTICAL ACCESSIBILITY REQUIREMENTS
 11-4.1.3(5).
  
 20) SHEET A4-05 MISSING DETAAIL 02/ A8.05.
  
 21) SHEET A4-04 & S-7 DETAIL #2 THE ELEVATOR SHAFT
 DETAIL IS MISSING THE SUMP PUMP DETAIL 09/A6.121 DETAIL
 NOT PROVIDED.
  
 22) TYPE II BUILDINGS REQUIRE A SPECIAL ONSITE
 INSPECTOR, BUILDINGS WITH UNUSUAL DESIGN OR METHODS OF
 CONSTRUCTION.
 NEW COMMENT
 -------------------------------------------------------
 ----------
  
 23) THERE IS A NEW 8X11 INTRODUCTORY OVERVIEW STATEMENT
 SHEET, INCLUDED IN THE PERMIT PACKAGE, AUTHOR UNKNOWN
 BUT THE COMMENT INDICATING THAT ALL INTERIOR FINISHES
 AND FINISH MATERIALS WILL BE SELECTED BY OWNER AND
 UNDER A SEPERATE CONTRACT SAID MATERIALS INCLUDE ALL
 FLOOR FINISHES, CEILING MATERIALS & FINISHES ALL WINDOW
 AND DOOR FINISHES, AND WALL SURFACE FINISHES.
  
 WITH THE ABOVE STATEMENT THE PERMIT CAN BE ISSUED AS A
 PROVISO, BUT A SECONDARY PERMIT WILL NEED TO BE APPLIED
 FOR BEFORE A C.O. WILL BE ISSUED.
 THE ARCHITECT OF RECORD SHOULD HAVE A STATEMENT ON THE
 PLANS INDICATING THAT FINISHES TO BE UNDER A SEPERATE
 PERMIT. 106.3.5.1.1. COMMERCIAL PLAN REVIEW CRITERIA
 WOULD REQUIRE THIS INFORMATION BEFORE A PERMIT COULD BE
 ISSUED, THAT WOULD BE THE REASON IT WOULD BE EXEMPTED
 FROM THIS PERMIT.
  
 24) THE NEW A SHEETS ARE SIGNED AND SEALED BUT NOT
 DATED.
 61G1-16.004 FL. ADMIN. CODE. PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 X= MISSING INFORMATION
 X - STATE THE FIRM NAME, ADDRESS AND TELEPHONE NUMBER
 X - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 X - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEALED
 INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING THE
 PLANS
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  