Plan Review Notes
Plan Review Notes For Permit 11050596
Permit Number 11050596
Review Stop M
Sequence Number 2
Notes
Date Text
2012-06-27 12:42:50 
  
 1. SEE PREVIOUS COMMENT LIST REGARDING SHAFT. IT NOW
 APPEARS THAT THE SHAFT HAS BEEN REMOVED FROM FLOOR
 PLANS, BUT DOUBLE RECTANGLES DRAWN IN DASHED LINES
 APPEAR ON THE MECHANICAL PLAN SHEETS FOR MEZZANINE AND
 CATWALK. FOR INSTANCE, SEE SHEET M2-2, COLUMN LINE 2
 BETWEEN A AND B. PLEASE PROVIDE INFORMATION OR REMOVE.
  
 A HORIZONTAL SHAFT IS SHOWN ON A SHEETS, BUILDING
 SECTIONS. PLEASE COORDINATE; MECHANICAL SHEETS DO NOT
 SHOW A SHAFT, SEE FBC MECHANICAL 607.5.5.
  
 2. FBC 2010 BUILDING 3006.2, SEE PREVIOUS COMMENT LIST,
 NO ELEVATOR MACHINE ROOM SHOWN. IF A MRL ELEVATOR IS
 PROPOSED, PLEASE SPECIFY ON MECHANICAL SHEETS OR ADVISE
 WHERE THIS INFORMATION CAN BE FOUND ON THE PLAN IN
 ORDER TO VERIFY THAT A SEPARATE, INDEPENDENT
 VENTILATION SYSTEM IS NOT REQUIRED. PROVIDE
 SPECIFICATIONS FOR THE ELEVATOR PROPOSED, FBC 107.1.
  
 3. SEE PREVIOUS LIST, PROVIDE EITHER A CURB DETAIL OR
 PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL FOR
 ROOF STANDS. DESIGNER IS TO SPECIFY DESIGN PRESSURES
 FOR ROOFTOP EQUIPMENT, FBC BUILDING 301.12, FAC9N-3.
  
 4. SEE PREVIOUS LIST, IF A SYSTEM SIZING SUMMARY IS
 PROVIDED IN LIEU OF A FULL COOLING LOAD CALCULATION, IT
 MUST BE SIGNED AND SEALED PER FBC BUILDING
 13-407.AB.1.1.
  
 5. FIRE DAMPERS ARE MISSING AT THE FOLLOWING LOCATIONS;
 8X10 EXHAUST DUCTS (TWO LOCATIONS), M2-1, AND RISERS
 BETWEEN FLOORS, EXHAUST THROUGH THE FLOOR M2-2. PLEASE
 CHECK ALL REQUIRED LOCATIONS AND REVISE. FBC MECHANICAL
 607.6.3, 607.5.3.
  
 6. LOCATION OF EXHAUST OUTLET NOT CLEAR, FBC MECHANICAL
 501.2.1. REVISE PLAN TO SHOW LOCATION.
  
 HAROLD MOSER, CHIEF MECHANICAL INSPECTOR
 561-805-6732
  
  
  
  