| 2012-06-27 12:42:50 | |
| | |
| | 1. SEE PREVIOUS COMMENT LIST REGARDING SHAFT. IT NOW |
| | APPEARS THAT THE SHAFT HAS BEEN REMOVED FROM FLOOR |
| | PLANS, BUT DOUBLE RECTANGLES DRAWN IN DASHED LINES |
| | APPEAR ON THE MECHANICAL PLAN SHEETS FOR MEZZANINE AND |
| | CATWALK. FOR INSTANCE, SEE SHEET M2-2, COLUMN LINE 2 |
| | BETWEEN A AND B. PLEASE PROVIDE INFORMATION OR REMOVE. |
| | |
| | A HORIZONTAL SHAFT IS SHOWN ON A SHEETS, BUILDING |
| | SECTIONS. PLEASE COORDINATE; MECHANICAL SHEETS DO NOT |
| | SHOW A SHAFT, SEE FBC MECHANICAL 607.5.5. |
| | |
| | 2. FBC 2010 BUILDING 3006.2, SEE PREVIOUS COMMENT LIST, |
| | NO ELEVATOR MACHINE ROOM SHOWN. IF A MRL ELEVATOR IS |
| | PROPOSED, PLEASE SPECIFY ON MECHANICAL SHEETS OR ADVISE |
| | WHERE THIS INFORMATION CAN BE FOUND ON THE PLAN IN |
| | ORDER TO VERIFY THAT A SEPARATE, INDEPENDENT |
| | VENTILATION SYSTEM IS NOT REQUIRED. PROVIDE |
| | SPECIFICATIONS FOR THE ELEVATOR PROPOSED, FBC 107.1. |
| | |
| | 3. SEE PREVIOUS LIST, PROVIDE EITHER A CURB DETAIL OR |
| | PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL FOR |
| | ROOF STANDS. DESIGNER IS TO SPECIFY DESIGN PRESSURES |
| | FOR ROOFTOP EQUIPMENT, FBC BUILDING 301.12, FAC9N-3. |
| | |
| | 4. SEE PREVIOUS LIST, IF A SYSTEM SIZING SUMMARY IS |
| | PROVIDED IN LIEU OF A FULL COOLING LOAD CALCULATION, IT |
| | MUST BE SIGNED AND SEALED PER FBC BUILDING |
| | 13-407.AB.1.1. |
| | |
| | 5. FIRE DAMPERS ARE MISSING AT THE FOLLOWING LOCATIONS; |
| | 8X10 EXHAUST DUCTS (TWO LOCATIONS), M2-1, AND RISERS |
| | BETWEEN FLOORS, EXHAUST THROUGH THE FLOOR M2-2. PLEASE |
| | CHECK ALL REQUIRED LOCATIONS AND REVISE. FBC MECHANICAL |
| | 607.6.3, 607.5.3. |
| | |
| | 6. LOCATION OF EXHAUST OUTLET NOT CLEAR, FBC MECHANICAL |
| | 501.2.1. REVISE PLAN TO SHOW LOCATION. |
| | |
| | HAROLD MOSER, CHIEF MECHANICAL INSPECTOR |
| | 561-805-6732 |
| | |
| | |
| | |
| | |