| 2012-03-05 11:46:10 | 114 SOUTH OLIVE AVENUE |
| | PERMIT #11050596 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION |
| | CODE 2007 EDITION: NFPA 1 AND NFPA 101 - 2006 EDITION |
| | WITH FLORIDA AMENDMENTS. |
| | |
| | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| | OF NFPA 241. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | PROVIDE A CIVIL ENGINEERING PLAN SHOWING UNDERGROUND |
| | UTILITIES, CONNECTIONS, FIRE HYDRANTS, PIPE SIZES ETC. |
| | |
| | PROVIDE TACTILE SIGNAGE AT EXIT DOORS. |
| | |
| | EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| | SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| | CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| | SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | SHEET A0.01: NFPA 5000 IS NOT ADOPTED BY THE STATE OF |
| | FLORIDA. |
| | |
| | SHEET A0.01: WHEN THE OCCUPANT LOAD EXCEEDS 300 PERSONS |
| | AND THE BUILDING IS FULLY SPRINKLERED, THE INTERIOR |
| | WALL AND CEILING FINISHES SHALL BE AS FOLLOWS: |
| | -ENCLOSED STAIRWAYS SHALL BE CLASS A OR B |
| | -CORRIDORS AND LOBBIES SHALL BE CLASS A, B OR C |
| | -GENERAL ASSEMBLY AREAS SHALL BE CLASS A, B OR C |
| | |
| | SHEET LS-01: PROVIDE HANDRAILS FOR STAIR #111. |
| | |
| | SHEET FP-01: LOBBY STEP AND GRAND STAIR LOBBY STEP |
| | SHALL HAVE A TREAD DEPTH OF AT LEAST 13-INCHES. PROVIDE |
| | A CONTRASTING STRIPE ON EACH STEPPING SURFACE OF THE |
| | LEADING EDGE OR TREAD NOSING TO MAKE THE PRESENCE OF AN |
| | ELEVATION CHANGE READILY APPARENT TO OCCUPANTS. |
| | |
| | SHEET A2-01: NO ROOM NAMES OR DOOR SCHEDULE PROVIDED |
| | FOR DOOR #118 AND #119. |
| | |
| | SHEET A2-03: STAIR DOOR #301 TO CATWALK SHALL BE LOCKED |
| | AT ALL TIMES. PERMANENT SIGN READING "AUTHORIZED |
| | PERSONNEL ONLY" SHALL BE AFFIXED TO THE DOOR. |
| | |
| | MEP SHEETS: PROJECT ADDRESS IS INCORRECTLY INDICATED AS |
| | "114 STONE STREET." |
| | |
| | SHEET F2-1: CIVIL PLANS NOT SUBMITTED SHOWING FIRE LINE |
| | CONNECTION TO CITY SUPPLY, BACKFLOW PREVENTER, FIRE |
| | HYDRANT LOCATION IN RELATION TO FDC, ETC. |
| | |
| | SHEET F2-1: FIRE DEPARTMENT CONNECTION SHALL BE LOCATED |
| | WITHIN 150 FEET OF A FIRE HYDRANT. LOCATE FDC ON OLIVE |
| | AVENUE. |
| | |
| | SHEET F3-1: PER FLORIDA ADMINISTRATIVE CODE SECTION |
| | 61G15-32.004, PLANS SHALL INDICATE THE HAZARD |
| | CLASSIFICATIONS, DESIGN DENSITIES, AND HYDRANT FLOW |
| | TEST DATA. |
| | |
| | SHEET E2-2: PLANS DO NOT INDICATE THE METHOD (HEAT |
| | DETECTOR/FLOW SWITCH WITHOUT TIME DELAY) USED TO SHUNT |
| | TRIP POWER TO THE ELEVATOR IN THE EVENT AN AUTOMATIC |
| | SPRINKLER ACTIVATES IN THE ELEVATOR MACHINE ROOM. |
| | |
| | SHEET A8-01: STAIR DOORS DO NOT HAVE A FIRE-RATING. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |