2012-03-05 11:46:10114 SOUTH OLIVE AVENUE
 PERMIT #11050596
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION: NFPA 1 AND NFPA 101 - 2006 EDITION
 WITH FLORIDA AMENDMENTS.
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE A CIVIL ENGINEERING PLAN SHOWING UNDERGROUND
 UTILITIES, CONNECTIONS, FIRE HYDRANTS, PIPE SIZES ETC.
  
 PROVIDE TACTILE SIGNAGE AT EXIT DOORS.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 SHEET A0.01: NFPA 5000 IS NOT ADOPTED BY THE STATE OF
 FLORIDA.
  
 SHEET A0.01: WHEN THE OCCUPANT LOAD EXCEEDS 300 PERSONS
 AND THE BUILDING IS FULLY SPRINKLERED, THE INTERIOR
 WALL AND CEILING FINISHES SHALL BE AS FOLLOWS:
 -ENCLOSED STAIRWAYS SHALL BE CLASS A OR B
 -CORRIDORS AND LOBBIES SHALL BE CLASS A, B OR C
 -GENERAL ASSEMBLY AREAS SHALL BE CLASS A, B OR C
  
 SHEET LS-01: PROVIDE HANDRAILS FOR STAIR #111.
  
 SHEET FP-01: LOBBY STEP AND GRAND STAIR LOBBY STEP
 SHALL HAVE A TREAD DEPTH OF AT LEAST 13-INCHES. PROVIDE
 A CONTRASTING STRIPE ON EACH STEPPING SURFACE OF THE
 LEADING EDGE OR TREAD NOSING TO MAKE THE PRESENCE OF AN
 ELEVATION CHANGE READILY APPARENT TO OCCUPANTS.
  
 SHEET A2-01: NO ROOM NAMES OR DOOR SCHEDULE PROVIDED
 FOR DOOR #118 AND #119.
  
 SHEET A2-03: STAIR DOOR #301 TO CATWALK SHALL BE LOCKED
 AT ALL TIMES. PERMANENT SIGN READING "AUTHORIZED
 PERSONNEL ONLY" SHALL BE AFFIXED TO THE DOOR.
  
 MEP SHEETS: PROJECT ADDRESS IS INCORRECTLY INDICATED AS
 "114 STONE STREET."
  
 SHEET F2-1: CIVIL PLANS NOT SUBMITTED SHOWING FIRE LINE
 CONNECTION TO CITY SUPPLY, BACKFLOW PREVENTER, FIRE
 HYDRANT LOCATION IN RELATION TO FDC, ETC.
  
 SHEET F2-1: FIRE DEPARTMENT CONNECTION SHALL BE LOCATED
 WITHIN 150 FEET OF A FIRE HYDRANT. LOCATE FDC ON OLIVE
 AVENUE.
  
 SHEET F3-1: PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, PLANS SHALL INDICATE THE HAZARD
 CLASSIFICATIONS, DESIGN DENSITIES, AND HYDRANT FLOW
 TEST DATA.
  
 SHEET E2-2: PLANS DO NOT INDICATE THE METHOD (HEAT
 DETECTOR/FLOW SWITCH WITHOUT TIME DELAY) USED TO SHUNT
 TRIP POWER TO THE ELEVATOR IN THE EVENT AN AUTOMATIC
 SPRINKLER ACTIVATES IN THE ELEVATOR MACHINE ROOM.
  
 SHEET A8-01: STAIR DOORS DO NOT HAVE A FIRE-RATING.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW