| 2012-02-28 14:22:16 | BUILDING PLAN REVIEW |
| | PERMIT: 11050596 |
| | ADD: 114 S OLIVE AVE |
| | CONT: LAKESIDE CONTRACTING CORP |
| | TEL: (954)553-8398 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | 2007/09 FLORIDA EXISTING BUILDING CODE W/ SUPPLEMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | FEB. 28/ 2012 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2) WHAT WAS THE LAST KNOWN USE FOR THIS BUILDING, IS |
| | THIS A CHANGE OF OCCUPANCY? THE PLANS DO NOT REFERENCE |
| | THE FLORIDA EXISTING BUILDING CODE AND TO WHICH TYPE OF |
| | COMPLIANCE METHOD THE PLANS WERE DESIGNED TOO? FL EXST |
| | BLDG CODE 101.5 (.1-.3). |
| | |
| | 3A) SEMI-COMPLIED. PLEASE REFER TO THE 2007 FBC-B FOR |
| | BUILDING TYPE, NOTE THE 2007FBC-B 603.1.3 REQUIRES ALL |
| | ROOF CONSTRUCTION GIRDERS, JOIST, TRUSSES AND DECKING |
| | ARE TO BE FIRE RETARDANT TREATED WOOD. SHEET S-5 |
| | INDICATES THE EXISTING 2X6 ROOF FRAMING, IS THE |
| | EXISTING STRUCTURE TRULY A BUILDING TYPE II-B? PLEASE |
| | NOTE THE NEW FRAMING MEMBERS LOCATED ON SHEET S-5 DO |
| | NOT INDICATE THE USE OF FIRE RETARDANT TREATED WOOD. |
| | |
| | 3B) COMPLIED. |
| | |
| | 4-7) COMPLIED. |
| | |
| | 8) 2ND REQUEST. PLEASE PROVIDE INFORMATION AS TO SHEET |
| | A2-01 & LS-01 WHAT IS THE ROOM # 119 USED FOR IS THIS |
| | THE ELEVATOR MACHINE ROOM? IF SO IT NEEDS TO BE RATED |
| | AS DOES THE DOOR. |
| | |
| | 9) 2ND REQUEST. SHEET A2-01 INDICATES NEW RAISED |
| | PLATFORM FLOORING PLEASE PROVIDE SQUARE FOOTAGE OF |
| | RAISED PLATFORM FLOORING, PLEASE REVIEW SECTION 2007/09 |
| | FBC-B 410.4 FIRE RETARDANT TREATED WOOD REQUIREMENT. |
| | |
| | 10) 2ND REQUEST. IT APPEARS THERE MAY BE A DISCREPANCY |
| | BETWEEN A2-01 & S-2, ON SHEET S-2 IT APPEARS THERE IS A |
| | DOORWAY THAT LEADS FROM THE RAISED DECK IN TO THE |
| | STAIRWELL WITH NO LANDING OR STAIRS. 106.1.2 ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 11) ROOF HATCH PLEASE BE AWARE OF ADDITIONAL |
| | INFORMATION REQUIRED, SHEET A8.01 INDICATES THE USE OF |
| | A NEW ROOF HATCH PLEASE SEE FBC-B 1013.5. & 2007/09 |
| | MECH CODE 304.10 FOR GUARD REQUIREMENTS WHEN UNITS ARE |
| | WITHIN 10'-0" OF THE ROOF EDGE. |
| | |
| | 11A) GUARDS SHALL BE PROVIDED WHERE APPLIANCES, |
| | EQUIPMENT, FANS, ROOF HATCH OPENINGS OR OTHER |
| | COMPONENTS THAT REQUIRE SERVICE ARE LOCATED WITHIN 10 |
| | FEET (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING |
| | SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN |
| | 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE |
| | BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT |
| | THE PASSAGE OF A 21-INCH-DIAMETER (533 MM) SPHERE. THE |
| | GUARD SHALL EXTEND NOT LESS THAN 30 INCHES (762 MM) |
| | BEYOND EACH END OF SUCH APPLIANCE, EQUIPMENT, FAN OR |
| | COMPONENT. |
| | |
| | 11B) 1013.6 ROOF ACCESS. GUARDS SHALL BE PROVIDED WHERE |
| | THE ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET (3048 |
| | MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE |
| | AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 |
| | INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. |
| | THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT THE |
| | PASSAGE OF A 21-INCH-DIAMETER (533 MM) SPHERE. |
| | |
| | |
| | 12) COMPLIED. |
| | 13) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR |
| | OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | 13A) WINDOWS |
| | 13B) ROOF HATCH |
| | 13C) A/C PRE-MANUFACTURED STANDS |
| | |
| | 14) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 15) MISSING DETAILS SHEET A5-01 STAIR # 1 INDICATES |
| | DETAIL 12 ON A-13 NO SHEET IS INDICATED ON THE |
| | ARCHITECTURAL INDEX. |
| | |
| | 15B) MISSING DETAIL SHEET A---02 STAIR # 2 IS MISSING |
| | DETAIL SHEET A-13 & A-14. |
| | |
| | 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | NEW COMMENTS |
| | |
| | 17) A4-03 & A4-04 : |
| | |
| | 17A) SEE DETAIL # 4 ON A-34 MISSING SHEET |
| | |
| | 17B) THE OLD PLANS INDICATE A ROOF / CEILING ASSEMBLY |
| | WITH A WIDE BLACK LINE. THE NEW PLANS INDICATE A |
| | SEPERATE WOOD ROOF JOIST SYSTEM AND A SEPERATE WOOD |
| | CEIING JOIST SYSTEM HOW ARE YOU GOING TO COMPLY AS A |
| | TYPE II-B BUILDING WITH NO COMBUSTIBLE FRAMING MEMBERS? |
| | 2007/09 FBC-B 603.1 & TABLE 601. |
| | |
| | 17C) A4-03 ALSO INDICATES A DETAIL # 11 SHEET A8.04 NOT |
| | IN PLANS? |
| | |
| | 18) SHEET LS-02 MEZZANINE RESTROOMS PLEASE SEE |
| | 11-411-4.1.3(11) IF TOILET ROOMS ARE PROVIDED, THEN |
| | EACH PUBLIC & COMMON USE TOILET ROOM SHALL COMPLY WITH |
| | 11-4.22. |
| | PLEASE REVIEW 11-4.22(1) DOORS SHALL NOT SWING INTO THE |
| | CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE. |
| | |
| | 19) 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | LS-01 THE VIP PLATFORM #108 & DANCE FLOOR # 107 WILL |
| | NEED TO COMPLY WITH VERTICAL ACCESSIBILITY REQUIREMENTS |
| | 11-4.1.3(5). |
| | |
| | 20) SHEET A4-05 MISSING DETAAIL 02/ A8.05. |
| | |
| | 21) SHEET A4-04 & S-7 DETAIL #2 THE ELEVATOR SHAFT |
| | DETAIL IS MISSING THE SUMP PUMP DETAIL 09/A6.121 DETAIL |
| | NOT PROVIDED. |
| | |
| | 22) TYPE II BUILDINGS REQUIRE A SPECIAL ONSITE |
| | INSPECTOR, BUILDINGS WITH UNUSUAL DESIGN OR METHODS OF |
| | CONSTRUCTION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |