Plan Review Notes
Plan Review Notes For Permit 11050596
Permit Number 11050596
Review Stop B
Sequence Number 2
Notes
Date Text
2012-02-28 14:22:16BUILDING PLAN REVIEW
 PERMIT: 11050596
 ADD: 114 S OLIVE AVE
 CONT: LAKESIDE CONTRACTING CORP
 TEL: (954)553-8398
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 2007/09 FLORIDA EXISTING BUILDING CODE W/ SUPPLEMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 FEB. 28/ 2012
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) WHAT WAS THE LAST KNOWN USE FOR THIS BUILDING, IS
 THIS A CHANGE OF OCCUPANCY? THE PLANS DO NOT REFERENCE
 THE FLORIDA EXISTING BUILDING CODE AND TO WHICH TYPE OF
 COMPLIANCE METHOD THE PLANS WERE DESIGNED TOO? FL EXST
 BLDG CODE 101.5 (.1-.3).
  
 3A) SEMI-COMPLIED. PLEASE REFER TO THE 2007 FBC-B FOR
 BUILDING TYPE, NOTE THE 2007FBC-B 603.1.3 REQUIRES ALL
 ROOF CONSTRUCTION GIRDERS, JOIST, TRUSSES AND DECKING
 ARE TO BE FIRE RETARDANT TREATED WOOD. SHEET S-5
 INDICATES THE EXISTING 2X6 ROOF FRAMING, IS THE
 EXISTING STRUCTURE TRULY A BUILDING TYPE II-B? PLEASE
 NOTE THE NEW FRAMING MEMBERS LOCATED ON SHEET S-5 DO
 NOT INDICATE THE USE OF FIRE RETARDANT TREATED WOOD.
  
 3B) COMPLIED.
  
 4-7) COMPLIED.
  
 8) 2ND REQUEST. PLEASE PROVIDE INFORMATION AS TO SHEET
 A2-01 & LS-01 WHAT IS THE ROOM # 119 USED FOR IS THIS
 THE ELEVATOR MACHINE ROOM? IF SO IT NEEDS TO BE RATED
 AS DOES THE DOOR.
  
 9) 2ND REQUEST. SHEET A2-01 INDICATES NEW RAISED
 PLATFORM FLOORING PLEASE PROVIDE SQUARE FOOTAGE OF
 RAISED PLATFORM FLOORING, PLEASE REVIEW SECTION 2007/09
 FBC-B 410.4 FIRE RETARDANT TREATED WOOD REQUIREMENT.
  
 10) 2ND REQUEST. IT APPEARS THERE MAY BE A DISCREPANCY
 BETWEEN A2-01 & S-2, ON SHEET S-2 IT APPEARS THERE IS A
 DOORWAY THAT LEADS FROM THE RAISED DECK IN TO THE
 STAIRWELL WITH NO LANDING OR STAIRS. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 11) ROOF HATCH PLEASE BE AWARE OF ADDITIONAL
 INFORMATION REQUIRED, SHEET A8.01 INDICATES THE USE OF
 A NEW ROOF HATCH PLEASE SEE FBC-B 1013.5. & 2007/09
 MECH CODE 304.10 FOR GUARD REQUIREMENTS WHEN UNITS ARE
 WITHIN 10'-0" OF THE ROOF EDGE.
  
 11A) GUARDS SHALL BE PROVIDED WHERE APPLIANCES,
 EQUIPMENT, FANS, ROOF HATCH OPENINGS OR OTHER
 COMPONENTS THAT REQUIRE SERVICE ARE LOCATED WITHIN 10
 FEET (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING
 SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN
 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE
 BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT
 THE PASSAGE OF A 21-INCH-DIAMETER (533 MM) SPHERE. THE
 GUARD SHALL EXTEND NOT LESS THAN 30 INCHES (762 MM)
 BEYOND EACH END OF SUCH APPLIANCE, EQUIPMENT, FAN OR
 COMPONENT.
  
 11B) 1013.6 ROOF ACCESS. GUARDS SHALL BE PROVIDED WHERE
 THE ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET (3048
 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE
 AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN 30
 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW.
 THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT THE
 PASSAGE OF A 21-INCH-DIAMETER (533 MM) SPHERE.
  
  
 12) COMPLIED.
 13) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 13A) WINDOWS
 13B) ROOF HATCH
 13C) A/C PRE-MANUFACTURED STANDS
  
 14) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 15) MISSING DETAILS SHEET A5-01 STAIR # 1 INDICATES
 DETAIL 12 ON A-13 NO SHEET IS INDICATED ON THE
 ARCHITECTURAL INDEX.
  
 15B) MISSING DETAIL SHEET A---02 STAIR # 2 IS MISSING
 DETAIL SHEET A-13 & A-14.
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 NEW COMMENTS
  
 17) A4-03 & A4-04 :
  
 17A) SEE DETAIL # 4 ON A-34 MISSING SHEET
  
 17B) THE OLD PLANS INDICATE A ROOF / CEILING ASSEMBLY
 WITH A WIDE BLACK LINE. THE NEW PLANS INDICATE A
 SEPERATE WOOD ROOF JOIST SYSTEM AND A SEPERATE WOOD
 CEIING JOIST SYSTEM HOW ARE YOU GOING TO COMPLY AS A
 TYPE II-B BUILDING WITH NO COMBUSTIBLE FRAMING MEMBERS?
 2007/09 FBC-B 603.1 & TABLE 601.
  
 17C) A4-03 ALSO INDICATES A DETAIL # 11 SHEET A8.04 NOT
 IN PLANS?
  
 18) SHEET LS-02 MEZZANINE RESTROOMS PLEASE SEE
 11-411-4.1.3(11) IF TOILET ROOMS ARE PROVIDED, THEN
 EACH PUBLIC & COMMON USE TOILET ROOM SHALL COMPLY WITH
 11-4.22.
 PLEASE REVIEW 11-4.22(1) DOORS SHALL NOT SWING INTO THE
 CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE.
  
 19) 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 LS-01 THE VIP PLATFORM #108 & DANCE FLOOR # 107 WILL
 NEED TO COMPLY WITH VERTICAL ACCESSIBILITY REQUIREMENTS
 11-4.1.3(5).
  
 20) SHEET A4-05 MISSING DETAAIL 02/ A8.05.
  
 21) SHEET A4-04 & S-7 DETAIL #2 THE ELEVATOR SHAFT
 DETAIL IS MISSING THE SUMP PUMP DETAIL 09/A6.121 DETAIL
 NOT PROVIDED.
  
 22) TYPE II BUILDINGS REQUIRE A SPECIAL ONSITE
 INSPECTOR, BUILDINGS WITH UNUSUAL DESIGN OR METHODS OF
 CONSTRUCTION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  