2011-05-24 08:28:32FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 MORE INFORMATION REQUESTED:
 1. SHEET A-1.0 BUILDING AND CODE INFORMATION CALLS FOR
 OCCUPANCY A-2, BUT GIVES NO OCCUPANT LOAD.
 THE NUMBER OF OCCUPANTS IS NEEDED FOR A FIXTURE COUNT.
 THE 2ND FLOOR SHOWS NO FACILITIES. IN THAT CASE THE
 FIXTURES ON THE MEZZANINE WOULD BE USED BY THE
 OCCUPANTS ON THE 2ND FLOOR
  
 2. MENS ADA RESTROOM ON SHEET A-41 DOES NOT MEET THE
 REQUIREMENTS FOR 11-4.17.3 SIZE AND ARRANGEMENT. THE
 SIZE AND ARRANGEMENT OF THE STANDARD TOILET STALL SHALL
 COMPLY WITH FIGURE 30(A)
  
 3. 403.7 UNISEX TOILET ROOM MAY, DEPENDING UPON FIXTURE
 COUNT, BE REQUIRED.
 403.7 UNISEX TOILET AND BATHING ROOMS. IN ASSEMBLY AND
 MERCANTILE OCCUPANCIES, AN ACCESSIBLE UNISEX TOILET
 ROOM SHALL BE PROVIDED WHERE AN AGGREGATE OF SIX OR
 MORE MALE AND FEMALE WATER CLOSETS IS REQUIRED.
  
 4. SHEET P3-1 ELEVATOR SUMP PUMP DETAIL DOES NOT SHOW
 THE SUMP PUMP OR PIPEING. FBC 3001.2 REFRENCED
 STANDARDS ASME A17.1 WHERE DRAINS ARE NOT PROVIDED TO
 PREVENT THE ACCUMULATION OF WATER, SUMP PUMPS SHALL BE
 PROVIDED.
  