| Plan Review Notes For Permit 11050596 |
| Permit Number |
11050596 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-05-24 08:28:32 | FBC PLUMBING 2007 REVIEW #1 | | | DENIED: | | | | | | MORE INFORMATION REQUESTED: | | | 1. SHEET A-1.0 BUILDING AND CODE INFORMATION CALLS FOR | | | OCCUPANCY A-2, BUT GIVES NO OCCUPANT LOAD. | | | THE NUMBER OF OCCUPANTS IS NEEDED FOR A FIXTURE COUNT. | | | THE 2ND FLOOR SHOWS NO FACILITIES. IN THAT CASE THE | | | FIXTURES ON THE MEZZANINE WOULD BE USED BY THE | | | OCCUPANTS ON THE 2ND FLOOR | | | | | | 2. MENS ADA RESTROOM ON SHEET A-41 DOES NOT MEET THE | | | REQUIREMENTS FOR 11-4.17.3 SIZE AND ARRANGEMENT. THE | | | SIZE AND ARRANGEMENT OF THE STANDARD TOILET STALL SHALL | | | COMPLY WITH FIGURE 30(A) | | | | | | 3. 403.7 UNISEX TOILET ROOM MAY, DEPENDING UPON FIXTURE | | | COUNT, BE REQUIRED. | | | 403.7 UNISEX TOILET AND BATHING ROOMS. IN ASSEMBLY AND | | | MERCANTILE OCCUPANCIES, AN ACCESSIBLE UNISEX TOILET | | | ROOM SHALL BE PROVIDED WHERE AN AGGREGATE OF SIX OR | | | MORE MALE AND FEMALE WATER CLOSETS IS REQUIRED. | | | | | | 4. SHEET P3-1 ELEVATOR SUMP PUMP DETAIL DOES NOT SHOW | | | THE SUMP PUMP OR PIPEING. FBC 3001.2 REFRENCED | | | STANDARDS ASME A17.1 WHERE DRAINS ARE NOT PROVIDED TO | | | PREVENT THE ACCUMULATION OF WATER, SUMP PUMPS SHALL BE | | | PROVIDED. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|