2011-06-17 15:52:40REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. DUCTS COMING FROM ROOF/SECOD FLOOR DOWN TO FIRST
 FLOOR ARE SHOWN IN RATED SHAFT ENCLOSURES. DUCTS WHICH
 PENETRATE SHAFT ENCLOSURES ARE REQUIRED TO BE PROTECTED
 BY BOTH FIRE AND SMOKE DAMPERS PER FBC-M 607.5.5. FYI:
 DUCTS THAT ONLY PENETRATE ONE FLOOR/CEILING ASSEMBLY
 MAY NOT NEED A SHAFT ENCLOSURE AND COULD BE COMPLIANT
 WITH A FIRE DAMPER PROTECTING THE PENETRATION AT THE
 SECOND FLOOR SLAB. THIS WOULD ELIMINATE THE NEED FOR
 SMOKE DAMPERS AND RATED SHAFTS.
  
 2. AHU 1 AND AHU 2 ON MEZZANINE LEVEL SHARE A COMMON
 RETURN AIR PLENUM. EACH UNIT IS REQUIRED TO HAVE DUCT
 MOUNTED SMOKE DTECTORS ON BUTH THE SUPPLY AND RETURN IN
 ACCORDANCE WITH FBC-M 606.2.2.
  
 3. THE ELEVATOR MACHINE ROOM DOES NOT APPEAR ON THE
 MECHANICAL FLOOR PLAN. HOW WILL THIS ROOM BE
 VENTILATED? A SEPARATE, INDEPENDENT VENTILATION OR AIR
 CONDITIONING SYSTEM IS REQUIRED FOR THE MACHINE ROOM
 PER FBC-B 3006.2.
  
 4. PAGE M2-1 SHOWS AHU-4 IN A CLOSET. NO SUCH APPLIANCE
 APPEARS ON THE EQUIPMENT SCHEDULE (PAGE M3-3). PLEASE
 COORDINATE SCHEDULES AND FLOOR PLANS.
  
 5. ROOF PLAN SHOWS A PRE-ENGINEERED A/C STAND FOR
 CONDENSING UNITS. PRODUCT APPROVAL IS REQUIRED PER FAC
 RULE 9N-3. PROVIDE PRODUCT APPROVAL WHICH IS APPROVED
 IN WRITING BY THE ENGINEER FOR THIS PROJECT PER FBC-M
 106.3.3.
  
 6. IF A SYSTEM SIZING SUMMARY IS PROVIDED IN LIEU OF A
 FULL COOLING LOAD CALCULATION, IT MUST BE SIGNED AND
 SEALED PER FBC-B 13-407.AB.1.1.
  